    Coupled Calculations of Data Center Cooling and Power Distribution Systems

    Source: Journal of Electronic Packaging:;2021:;volume( 144 ):;issue: 004::page 41002-1
    Author:
    Wemhoff, Aaron P.
    ,
    Ahmed, Faisal
    DOI: 10.1115/1.4052101
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: Physics-based modeling aids in designing efficient data center power and cooling systems. These systems have traditionally been modeled independently under the assumption that the inherent coupling of effects between the systems has negligible impact. This study tests the assumption through uncertainty quantification of models for a typical 300 kW data center supplied through either an alternating current (AC)-based or direct current (DC)-based power distribution system. A novel calculation scheme is introduced that couples the calculations of these two systems to estimate the resultant impact on predicted power usage effectiveness (PUE), computer room air conditioning (CRAC) return temperature, total system power requirement, and system power loss values. A two-sample z-test for comparing means is used to test for statistical significance with 95% confidence. The power distribution component efficiencies are calibrated to available published and experimental data. The predictions for a typical data center with an AC-based system suggest that the coupling of system calculations results in statistically significant differences for the cooling system PUE, the overall PUE, the CRAC return air temperature, and total electrical losses. However, none of the tested metrics are statistically significant for a DC-based system. The predictions also suggest that a DC-based system provides statistically significant lower overall PUE and electrical losses compared to the AC-based system, but only when coupled calculations are used. These results indicate that the coupled calculations impact predicted general energy efficiency metrics and enable statistically significant conclusions when comparing different data center cooling and power distribution strategies.
    • Download: (710.3Kb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Price: 5000 Rial
    • Statistics

      Coupled Calculations of Data Center Cooling and Power Distribution Systems

    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/4284746
    Collections
    • Journal of Electronic Packaging

    Show full item record

    contributor authorWemhoff, Aaron P.
    contributor authorAhmed, Faisal
    date accessioned2022-05-08T09:07:05Z
    date available2022-05-08T09:07:05Z
    date copyright10/6/2021 12:00:00 AM
    date issued2021
    identifier issn1043-7398
    identifier otherep_144_04_041002.pdf
    identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4284746
    description abstractPhysics-based modeling aids in designing efficient data center power and cooling systems. These systems have traditionally been modeled independently under the assumption that the inherent coupling of effects between the systems has negligible impact. This study tests the assumption through uncertainty quantification of models for a typical 300 kW data center supplied through either an alternating current (AC)-based or direct current (DC)-based power distribution system. A novel calculation scheme is introduced that couples the calculations of these two systems to estimate the resultant impact on predicted power usage effectiveness (PUE), computer room air conditioning (CRAC) return temperature, total system power requirement, and system power loss values. A two-sample z-test for comparing means is used to test for statistical significance with 95% confidence. The power distribution component efficiencies are calibrated to available published and experimental data. The predictions for a typical data center with an AC-based system suggest that the coupling of system calculations results in statistically significant differences for the cooling system PUE, the overall PUE, the CRAC return air temperature, and total electrical losses. However, none of the tested metrics are statistically significant for a DC-based system. The predictions also suggest that a DC-based system provides statistically significant lower overall PUE and electrical losses compared to the AC-based system, but only when coupled calculations are used. These results indicate that the coupled calculations impact predicted general energy efficiency metrics and enable statistically significant conclusions when comparing different data center cooling and power distribution strategies.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleCoupled Calculations of Data Center Cooling and Power Distribution Systems
    typeJournal Paper
    journal volume144
    journal issue4
    journal titleJournal of Electronic Packaging
    identifier doi10.1115/1.4052101
    journal fristpage41002-1
    journal lastpage41002-9
    page9
    treeJournal of Electronic Packaging:;2021:;volume( 144 ):;issue: 004
    contenttypeFulltext