Impact of Tile Design on the Thermal Performance of Open and Enclosed AislesSource: Journal of Electronic Packaging:;2018:;volume( 140 ):;issue: 001::page 10907DOI: 10.1115/1.4039028Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: In raised floor data centers, tiles with high open area ratio or complex understructure are used to fulfill the demand of today's high-density computing. Using more open tiles reduces the pressure drop across the raised floor with the potential advantages of increased airflow and lower noise. However, it introduces the disadvantage of increased nonuniformity of airflow distribution. In addition, there are various tile designs available on the market with different opening shapes or understructures. Furthermore, a physical separation of cold and hot aisles (containment) has been introduced to minimize the mixing of cold and hot air. In this study, three types of floor tiles with different open area, opening geometry, and understructure are considered. Experimentally validated detail models of tiles were implemented in computational fluid dynamics (CFD) simulations to address the impact of tile design on the cooling of information technology (IT) equipment in both open and enclosed aisle configurations. Also, impacts of under-cabinet leakage on the IT equipment inlet temperature in the provisioned and under-provisioned scenarios are studied. In addition, a predictive equation for the critical under-provisioning point that can lead to a no-flow condition in IT equipment with weaker airflow systems is presented. Finally, the impact of tile design on thermal performance in a partially enclosed aisle with entrance doors is studied and discussed.
|
Collections
Show full item record
contributor author | Khalili, Sadegh | |
contributor author | Tradat, Mohammad I. | |
contributor author | Nemati, Kourosh | |
contributor author | Seymour, Mark | |
contributor author | Sammakia, Bahgat | |
date accessioned | 2019-02-28T11:14:15Z | |
date available | 2019-02-28T11:14:15Z | |
date copyright | 3/2/2018 12:00:00 AM | |
date issued | 2018 | |
identifier issn | 1043-7398 | |
identifier other | ep_140_01_010907.pdf | |
identifier uri | http://yetl.yabesh.ir/yetl1/handle/yetl/4254158 | |
description abstract | In raised floor data centers, tiles with high open area ratio or complex understructure are used to fulfill the demand of today's high-density computing. Using more open tiles reduces the pressure drop across the raised floor with the potential advantages of increased airflow and lower noise. However, it introduces the disadvantage of increased nonuniformity of airflow distribution. In addition, there are various tile designs available on the market with different opening shapes or understructures. Furthermore, a physical separation of cold and hot aisles (containment) has been introduced to minimize the mixing of cold and hot air. In this study, three types of floor tiles with different open area, opening geometry, and understructure are considered. Experimentally validated detail models of tiles were implemented in computational fluid dynamics (CFD) simulations to address the impact of tile design on the cooling of information technology (IT) equipment in both open and enclosed aisle configurations. Also, impacts of under-cabinet leakage on the IT equipment inlet temperature in the provisioned and under-provisioned scenarios are studied. In addition, a predictive equation for the critical under-provisioning point that can lead to a no-flow condition in IT equipment with weaker airflow systems is presented. Finally, the impact of tile design on thermal performance in a partially enclosed aisle with entrance doors is studied and discussed. | |
publisher | The American Society of Mechanical Engineers (ASME) | |
title | Impact of Tile Design on the Thermal Performance of Open and Enclosed Aisles | |
type | Journal Paper | |
journal volume | 140 | |
journal issue | 1 | |
journal title | Journal of Electronic Packaging | |
identifier doi | 10.1115/1.4039028 | |
journal fristpage | 10907 | |
journal lastpage | 010907-12 | |
tree | Journal of Electronic Packaging:;2018:;volume( 140 ):;issue: 001 | |
contenttype | Fulltext |