    Data Center Housing High Performance Supercomputer Cluster: Above Floor Thermal Measurements Compared To CFD Analysis

    Source: Journal of Electronic Packaging:;2010:;volume( 132 ):;issue: 002::page 21009
    Author:
    Roger Schmidt
    ,
    Joe Caricari
    ,
    Madhusudan Iyengar
    DOI: 10.1115/1.4001871
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: With the ever increasing heat dissipated by information technology (IT) equipment housed in data centers, it is becoming more important to project the changes that can occur in the data center as the newer higher powered hardware is installed. The computational fluid dynamics (CFD) software that is available has improved over the years. CFD software specific to data center thermal analysis has also been developed. This has improved the time lines of providing some quick analysis of the effects of new hardware into the data center. But it is critically important that this software provide a good report to the user of the effects of adding this new hardware. It is the purpose of this paper to examine a large cluster installation and compare the CFD analysis with environmental measurements obtained from the same site. This paper shows measurements and CFD data for high powered racks as high as 27 kW clustered such that heat fluxes in some regions of the data center exceeded 700 W per square foot. This paper describes the thermal profile of a high performance computing cluster located in an data center and a comparison of that cluster modeled via CFD. The high performance advanced simulation and computing (ASC) cluster had a peak performance of 77.8 TFlop/s, and employed more than 12,000 processors, 50 Tbytes of memory, and 2 Pbytes of globally accessible disk space. The cluster was first tested in the manufacturer’s development laboratory in Poughkeepsie, New York, and then shipped to Lawrence Livermore National Laboratory in Livermore, California, where it was installed to support the national security mission of the U.S. Detailed measurements were taken in both data centers and were previously reported. The Poughkeepsie results will be reported here along with a comparison to CFD modeling results. In some areas of the Poughkeepsie data center, there were regions that did exceed the equipment inlet air temperature specifications by a significant amount. These areas will be highlighted and reasons given on why these areas failed to meet the criteria. The modeling results by region showed trends that compared somewhat favorably but some rack thermal profiles deviated quite significantly from measurements.
    keyword(s): Measurement , Computational fluid dynamics , Data centers , Temperature AND Air flow ,
    • Download: (1.462Mb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Price: 5000 Rial
    • Statistics

      Data Center Housing High Performance Supercomputer Cluster: Above Floor Thermal Measurements Compared To CFD Analysis

    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/142964
    Collections
    • Journal of Electronic Packaging

    Show full item record

    contributor authorRoger Schmidt
    contributor authorJoe Caricari
    contributor authorMadhusudan Iyengar
    date accessioned2017-05-09T00:37:14Z
    date available2017-05-09T00:37:14Z
    date copyrightJune, 2010
    date issued2010
    identifier issn1528-9044
    identifier otherJEPAE4-26304#021009_1.pdf
    identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/142964
    description abstractWith the ever increasing heat dissipated by information technology (IT) equipment housed in data centers, it is becoming more important to project the changes that can occur in the data center as the newer higher powered hardware is installed. The computational fluid dynamics (CFD) software that is available has improved over the years. CFD software specific to data center thermal analysis has also been developed. This has improved the time lines of providing some quick analysis of the effects of new hardware into the data center. But it is critically important that this software provide a good report to the user of the effects of adding this new hardware. It is the purpose of this paper to examine a large cluster installation and compare the CFD analysis with environmental measurements obtained from the same site. This paper shows measurements and CFD data for high powered racks as high as 27 kW clustered such that heat fluxes in some regions of the data center exceeded 700 W per square foot. This paper describes the thermal profile of a high performance computing cluster located in an data center and a comparison of that cluster modeled via CFD. The high performance advanced simulation and computing (ASC) cluster had a peak performance of 77.8 TFlop/s, and employed more than 12,000 processors, 50 Tbytes of memory, and 2 Pbytes of globally accessible disk space. The cluster was first tested in the manufacturer’s development laboratory in Poughkeepsie, New York, and then shipped to Lawrence Livermore National Laboratory in Livermore, California, where it was installed to support the national security mission of the U.S. Detailed measurements were taken in both data centers and were previously reported. The Poughkeepsie results will be reported here along with a comparison to CFD modeling results. In some areas of the Poughkeepsie data center, there were regions that did exceed the equipment inlet air temperature specifications by a significant amount. These areas will be highlighted and reasons given on why these areas failed to meet the criteria. The modeling results by region showed trends that compared somewhat favorably but some rack thermal profiles deviated quite significantly from measurements.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleData Center Housing High Performance Supercomputer Cluster: Above Floor Thermal Measurements Compared To CFD Analysis
    typeJournal Paper
    journal volume132
    journal issue2
    journal titleJournal of Electronic Packaging
    identifier doi10.1115/1.4001871
    journal fristpage21009
    identifier eissn1043-7398
    keywordsMeasurement
    keywordsComputational fluid dynamics
    keywordsData centers
    keywordsTemperature AND Air flow
    treeJournal of Electronic Packaging:;2010:;volume( 132 ):;issue: 002
    contenttypeFulltext