contributor author | David Ruch | |
contributor author | David E. Claridge | |
date accessioned | 2017-05-08T23:39:31Z | |
date available | 2017-05-08T23:39:31Z | |
date copyright | May, 1992 | |
date issued | 1992 | |
identifier issn | 0199-6231 | |
identifier other | JSEEDO-28237#77_1.pdf | |
identifier uri | http://yetl.yabesh.ir/yetl/handle/yetl/110830 | |
description abstract | This paper develops a four-parameter change-point model of energy consumption as a function of dry-bulb temperature, along with accompanying error diagnostics for the model’s parameters. The model is a generalization of the widely used three-parameter, or variable-base degree-day method. The model is applied to data from a case study grocery store, is compared to the three-parameter PRISM CO model of the store data, and is shown to provide a statistically better fit to consumption data below about 15°C. This model appears to be useful for diagnosing unexpected energy use in some buildings and should be useful for determining retrofit energy savings from monitored pre-retrofit and post-retrofit data for the class of buildings whose pre-retrofit consumption is fit by a four-parameter linear change-point model. | |
publisher | The American Society of Mechanical Engineers (ASME) | |
title | A Four-Parameter Change-Point Model for Predicting Energy Consumption in Commercial Buildings | |
type | Journal Paper | |
journal volume | 114 | |
journal issue | 2 | |
journal title | Journal of Solar Energy Engineering | |
identifier doi | 10.1115/1.2929993 | |
journal fristpage | 77 | |
journal lastpage | 83 | |
identifier eissn | 1528-8986 | |
keywords | Structures | |
keywords | Energy consumption | |
keywords | Errors | |
keywords | Prisms (Optics) AND Temperature | |
tree | Journal of Solar Energy Engineering:;1992:;volume( 114 ):;issue: 002 | |
contenttype | Fulltext | |