Experimental Investigation of the Humidification Parameters in a Vertically Aligned Triple Pad Multistage Evaporative CoolerSource: Journal of Thermal Science and Engineering Applications:;2022:;volume( 014 ):;issue: 012::page 121012DOI: 10.1115/1.4055262Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: The present work involves designing and fabricating the threestage humidifier test rig where three Celdek 7090 packings are arranged vertically at equidistance, forming a multistage humidifier. Water flowrate and airflow rates are regulated to obtain required humidification under both singlepad and threepad configurations. Output variables like the coefficient of performance, evaporation rate, cooling effect, cooling efficiency, and pressure drop are determined. Results indicated that threestage packing gave high performance compared to the single stage. Changes in temperature, change in humidity, saturation efficiency, and coefficient of performance values are 6.5 °C, 44%, 80%, and 2.1, respectively, are the maximum values noticed for the multistage humidifier. The study indicated that with the increase in the rate of water flow, there is a rise in performance parameters till a water flowrate of 0.6 l per minute, and after this value, performance deteriorates. Even though multistage performs better than a single stage, as the number of stages increases, the stagewise performance declines.
|
Show full item record
contributor author | Salins, Sampath Suranjan;Kumar, Shiva;Kota Reddy, S.V.;Ajith, Krishna | |
date accessioned | 2023-04-06T13:00:29Z | |
date available | 2023-04-06T13:00:29Z | |
date copyright | 9/22/2022 12:00:00 AM | |
date issued | 2022 | |
identifier issn | 19485085 | |
identifier other | tsea_14_12_121012.pdf | |
identifier uri | http://yetl.yabesh.ir/yetl1/handle/yetl/4288911 | |
description abstract | The present work involves designing and fabricating the threestage humidifier test rig where three Celdek 7090 packings are arranged vertically at equidistance, forming a multistage humidifier. Water flowrate and airflow rates are regulated to obtain required humidification under both singlepad and threepad configurations. Output variables like the coefficient of performance, evaporation rate, cooling effect, cooling efficiency, and pressure drop are determined. Results indicated that threestage packing gave high performance compared to the single stage. Changes in temperature, change in humidity, saturation efficiency, and coefficient of performance values are 6.5 °C, 44%, 80%, and 2.1, respectively, are the maximum values noticed for the multistage humidifier. The study indicated that with the increase in the rate of water flow, there is a rise in performance parameters till a water flowrate of 0.6 l per minute, and after this value, performance deteriorates. Even though multistage performs better than a single stage, as the number of stages increases, the stagewise performance declines. | |
publisher | The American Society of Mechanical Engineers (ASME) | |
title | Experimental Investigation of the Humidification Parameters in a Vertically Aligned Triple Pad Multistage Evaporative Cooler | |
type | Journal Paper | |
journal volume | 14 | |
journal issue | 12 | |
journal title | Journal of Thermal Science and Engineering Applications | |
identifier doi | 10.1115/1.4055262 | |
journal fristpage | 121012 | |
journal lastpage | 12101212 | |
page | 12 | |
tree | Journal of Thermal Science and Engineering Applications:;2022:;volume( 014 ):;issue: 012 | |
contenttype | Fulltext |