Show simple item record

contributor authorShah, Jimil M.
contributor authorPadmanaban, Keerthivasan
contributor authorSingh, Hrishabh
contributor authorDuraisamy Asokan, Surya
contributor authorSaini, Satyam
contributor authorAgonafer, Dereje
date accessioned2022-05-08T09:05:44Z
date available2022-05-08T09:05:44Z
date copyright10/14/2021 12:00:00 AM
date issued2021
identifier issn1043-7398
identifier otherep_144_02_021109.pdf
identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4284725
description abstractThe adoption of single-phase liquid immersion cooling (Sp-LIC) for Information Technology equipment provides an excellent cooling platform coupled with significant energy savings. There are, however, very limited studies related to the reliability of such cooling technology. The accelerated thermal cycling (ATC) test given ATC JEDEC is relevant just for air cooling but there is no such standard for immersion cooling. The ASTM benchmark D3455 with some appropriate adjustments was adopted to test the material compatibility because of the air and dielectric fluid differences in the heat capacitance property and corresponding ramp rate during thermal cycling. For this study, accelerated thermal degradation of the printed circuit board (PCB), passive components, and fiber optic cables submerged in air, white mineral oil, and synthetic fluid at a hoisted temperature of 45 °C and 35% humidity is undertaken. This paper serves multiple purposes including designing experiments, testing and evaluating material compatibility of PCB, passive components, and optical fibers in different hydrocarbon oils for single-phase immersion cooling. Samples of different materials were immersed in different hydrocarbon oils and air and kept in an environmental chamber at 45 °C for a total of 288 h. Samples were then evaluated for their mechanical and electrical properties using dynamic mechanical analyzer (DMA) and a multimeter, respectively. The cross section of some samples was also investigated for their structural integrity using scanning electron microscope (SEM). The literature gathered on the subject and quantifiable data gathered by the authors provide the primary basis for this research document.
publisherThe American Society of Mechanical Engineers (ASME)
titleEvaluating the Reliability of Passive Server Components for Single-Phase Immersion Cooling
typeJournal Paper
journal volume144
journal issue2
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.4052536
journal fristpage21109-1
journal lastpage21109-8
page8
treeJournal of Electronic Packaging:;2021:;volume( 144 ):;issue: 002
contenttypeFulltext