Heat Transfer Characteristics of Passive Condensers for Reactor Containment CoolingSource: Journal of Thermal Science and Engineering Applications:;2013:;volume( 005 ):;issue: 002::page 21002Author:Revankar, Shripad T.
DOI: 10.1115/1.4023600Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: Passive condensers that are based on gravitational force do not require pumps or blowers to move fluid and, hence, are considered as safety measures in nuclear power plant containment cooling. In this paper vertical tube passive condensers with the tube inside condensation and cooled by a secondary pool of water are discussed as applied to reactor containment heat removal system. Series of experiments were carried out on scaled separate effects test facilities with vertical single tube and four tube bundle condensers. The results of experimental data on the rate of condensation heat transfer, the effects of noncondensable, and parametric effects, such as pressure, tube diameters and lengths, obtained from single tube and tube bundle passive condenser are presented. The data on the tube bundle indicated larger condensation heat transfer due to enhanced heat transfer in the secondary cooling. For tube bundle condensation, the turbulent mixing on the secondary pool side decreases the temperature difference between pool water and condenser tube outer wall, causing an increase in secondary heat transfer. Theoretical models on tube condensation based on heat and mass analogy and boundary layer models were developed. The data were compared with theoretical models and good agreement was observed between theoretical predictions and single tube condensation heat transfer data. For the tube bundle condenser, the theoretical model agreed with data when the secondary side enhancement in heat transfer due to turbulent mixing in the flow boiling was included. Practical heat transfer correlations are presented using available data on passive condensers for reactor application.
|
Show full item record
contributor author | Revankar, Shripad T. | |
date accessioned | 2017-05-09T01:02:49Z | |
date available | 2017-05-09T01:02:49Z | |
date issued | 2013 | |
identifier issn | 1948-5085 | |
identifier other | tsea_5_2_021002.pdf | |
identifier uri | http://yetl.yabesh.ir/yetl/handle/yetl/153226 | |
description abstract | Passive condensers that are based on gravitational force do not require pumps or blowers to move fluid and, hence, are considered as safety measures in nuclear power plant containment cooling. In this paper vertical tube passive condensers with the tube inside condensation and cooled by a secondary pool of water are discussed as applied to reactor containment heat removal system. Series of experiments were carried out on scaled separate effects test facilities with vertical single tube and four tube bundle condensers. The results of experimental data on the rate of condensation heat transfer, the effects of noncondensable, and parametric effects, such as pressure, tube diameters and lengths, obtained from single tube and tube bundle passive condenser are presented. The data on the tube bundle indicated larger condensation heat transfer due to enhanced heat transfer in the secondary cooling. For tube bundle condensation, the turbulent mixing on the secondary pool side decreases the temperature difference between pool water and condenser tube outer wall, causing an increase in secondary heat transfer. Theoretical models on tube condensation based on heat and mass analogy and boundary layer models were developed. The data were compared with theoretical models and good agreement was observed between theoretical predictions and single tube condensation heat transfer data. For the tube bundle condenser, the theoretical model agreed with data when the secondary side enhancement in heat transfer due to turbulent mixing in the flow boiling was included. Practical heat transfer correlations are presented using available data on passive condensers for reactor application. | |
publisher | The American Society of Mechanical Engineers (ASME) | |
title | Heat Transfer Characteristics of Passive Condensers for Reactor Containment Cooling | |
type | Journal Paper | |
journal volume | 5 | |
journal issue | 2 | |
journal title | Journal of Thermal Science and Engineering Applications | |
identifier doi | 10.1115/1.4023600 | |
journal fristpage | 21002 | |
journal lastpage | 21002 | |
identifier eissn | 1948-5093 | |
tree | Journal of Thermal Science and Engineering Applications:;2013:;volume( 005 ):;issue: 002 | |
contenttype | Fulltext |