description abstractIn the drive to enhance data center energy efficiency, much attention has been placed on the prospect of airflow containment in hot-aisle cold-aisle raised floor arrangements. Such containment prevents airflow recirculation, eliminating the mixing effects of the hot and cold air streams that can cause an undesirable temperature rise at the inlet of the equipment racks. The intuitive assessment of the industry has been that the elimination of such mixing effects increases the energy efficiency of the data center cooling system by enabling delivery of air at higher inlet temperatures, thus reducing the amount of infrastructure cooling required. This paper employs an end-to-end modeling approach to analyze the effect of air stream containment in the computer room and its impact on the holistic system efficiency. Dimensionless heat index parameters are employed to characterize the effects of containment, recirculation, and mixing within the computer room environment. The extent of recirculation is shown to primarily influence the operation of the rack and computer room air conditioning (CRAC) level cooling systems, with the chiller systems also impacted. The overall effect on the complete cooling system performance and data center efficiency requires balancing of these effects. Through this model analysis, it is shown that containment may negatively impact overall energy efficiency in some circumstances, and that recirculation may actually be beneficial to overall energy efficiency under certain system dependent operating thresholds.
publisherThe American Society of Mechanical Engineers (ASME)
titleFrom Chip to Cooling Tower Data Center Modeling: Influence of Air-Stream Containment on Operating Efficiencyor1
typeJournal Paper
journal volume134
journal issue4
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.4007110
journal fristpage41006
identifier eissn1043-7398
keywordsHeat
keywordsTemperature
keywordsData centers
keywordsHeat sinks
keywordsContainment
keywordsModeling
keywordsAir flow AND Temperature control
treeJournal of Electronic Packaging:;2012:;volume( 134 ):;issue: 004
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record