Show simple item record

contributor authorR. A. Wirtz
contributor authorAshok Mathur
date accessioned2017-05-08T23:43:59Z
date available2017-05-08T23:43:59Z
date copyrightMarch, 1994
date issued1994
identifier issn1528-9044
identifier otherJEPAE4-26141#49_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/113461
description abstractMeasurements of the distribution of convective heat transfer over the five exposed faces of a low profile electronic package are described. The package, of square planform and length-to-height ratio, L/a = 6 , is part of a regular array of such elements attached to one wall of a low aspect ratio channel. The coolant is air, and experiments are described for the Reynolds number range, 3000<Re<7000. The average heat transfer coefficient for the top face is found to be nearly equal to the overall average heat transfer coefficient for the element. The average heat transfer coefficient for the upstream face and two side faces are higher than the overall average by approximately 30–40 percent and 20–30 percent, respectively while that for the downstream face is 20–30 percent less than the overall average. Furthermore, the distribution in local heat transfer coefficient over the five surfaces of the element is approximately independent of variations in Reynolds number.
publisherThe American Society of Mechanical Engineers (ASME)
titleConvective Heat Transfer Distribution on the Surface of an Electronic Package
typeJournal Paper
journal volume116
journal issue1
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.2905493
journal fristpage49
journal lastpage54
identifier eissn1043-7398
keywordsConvection
keywordsElectronic packages
keywordsHeat transfer coefficients
keywordsReynolds number
keywordsCoolants
keywordsChannels (Hydraulic engineering) AND Measurement
treeJournal of Electronic Packaging:;1994:;volume( 116 ):;issue: 001
contenttypeFulltext