    Use of Simplified System Models to Measure Retrofit Energy Savings

    Source: Journal of Solar Energy Engineering:;1993:;volume( 115 ):;issue: 002::page 57
    Author:
    S. Katipamula
    ,
    D. E. Claridge
    DOI: 10.1115/1.2930033
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: The retrofit of dual-duct constant volume systems (DDCV) with energy-efficient variable air volume systems (VAV) has become common in recent years. In general, the energy savings from such retrofits are estimated by developing a temperature-dependent regression model using whole building preretrofit energy consumption data. Model predictions are then compared with measured post retrofit consumption, to determine the savings. In cases where the preretrofit energy consumption is not available such a method cannot be implemented. This paper describes a method that can be used to calculate savings in such cases. The method is based on use of simplified calibrated system models. A VAV model was developed based on the ASHRAE TC 4.7 Simplified Energy Analysis Procedure (SEAP) (Knebel, 1983) and calibrated with the postretrofit energy consumption of a large engineering center in Central Texas. The loads from the calibrated VAV model were then used with the DDCV model to estimate the preretrofit energy use, also based on TC 4.7 SEAP, and apparent savings were determined as the difference between the DDCV predicted consumption and measured energy consumption for the postretrofit VAV system. The simulated hourly cooling energy consumption from the VAV model was within ±1GJ (±20 percent) of the measured consumption. The simulated daily consumption (the sum of 24 hours of consumption) compared better with the measured daily consumption (within ±7 percent). The apparent saving from the retrofit of the DDCV system with VAV was about 684 GJ in cooling energy and 324 GJ in heating energy for a three-week period June–July 1991.
    • Download: (911.7Kb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Price: 5000 Rial
    • Statistics

      Use of Simplified System Models to Measure Retrofit Energy Savings

    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/112594
    Collections
    • Journal of Solar Energy Engineering

    Show full item record

    contributor authorS. Katipamula
    contributor authorD. E. Claridge
    date accessioned2017-05-08T23:42:30Z
    date available2017-05-08T23:42:30Z
    date copyrightMay, 1993
    date issued1993
    identifier issn0199-6231
    identifier otherJSEEDO-28243#57_1.pdf
    identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/112594
    description abstractThe retrofit of dual-duct constant volume systems (DDCV) with energy-efficient variable air volume systems (VAV) has become common in recent years. In general, the energy savings from such retrofits are estimated by developing a temperature-dependent regression model using whole building preretrofit energy consumption data. Model predictions are then compared with measured post retrofit consumption, to determine the savings. In cases where the preretrofit energy consumption is not available such a method cannot be implemented. This paper describes a method that can be used to calculate savings in such cases. The method is based on use of simplified calibrated system models. A VAV model was developed based on the ASHRAE TC 4.7 Simplified Energy Analysis Procedure (SEAP) (Knebel, 1983) and calibrated with the postretrofit energy consumption of a large engineering center in Central Texas. The loads from the calibrated VAV model were then used with the DDCV model to estimate the preretrofit energy use, also based on TC 4.7 SEAP, and apparent savings were determined as the difference between the DDCV predicted consumption and measured energy consumption for the postretrofit VAV system. The simulated hourly cooling energy consumption from the VAV model was within ±1GJ (±20 percent) of the measured consumption. The simulated daily consumption (the sum of 24 hours of consumption) compared better with the measured daily consumption (within ±7 percent). The apparent saving from the retrofit of the DDCV system with VAV was about 684 GJ in cooling energy and 324 GJ in heating energy for a three-week period June–July 1991.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleUse of Simplified System Models to Measure Retrofit Energy Savings
    typeJournal Paper
    journal volume115
    journal issue2
    journal titleJournal of Solar Energy Engineering
    identifier doi10.1115/1.2930033
    journal fristpage57
    journal lastpage68
    identifier eissn1528-8986
    treeJournal of Solar Energy Engineering:;1993:;volume( 115 ):;issue: 002
    contenttypeFulltext
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian
     
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian