    Development of Nondimensional Cycling Model for Estimating the Seasonal Performance of Air Conditioners

    Source: Journal of Solar Energy Engineering:;1993:;volume( 115 ):;issue: 003::page 176
    Author:
    D. L. O’Neal
    ,
    S. Katipamula
    DOI: 10.1115/1.2930046
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: A nondimensional cycling model for estimating the seasonal performance of conventional air conditioners and heat pumps was developed. Starting with a simple time-constant model of the startup of an air conditioner, a nondimensional time variable was developed which captures three important influences of on-off cycling performance degradation: response of the system, fraction on-time of the system, and cycling rate. Experimental data from three air conditioners and one heat pump provided excellent agreement with the model. The model should be applicable to any cooling technology that has similar on-off characteristics to conventional air conditioners and heat pumps.
    keyword(s): Air conditioners , Heat pumps AND Cooling ,
    • Download: (490.3Kb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Price: 5000 Rial
    • Statistics

      Development of Nondimensional Cycling Model for Estimating the Seasonal Performance of Air Conditioners

    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/112588
    Collections
    • Journal of Solar Energy Engineering

    Show full item record

    contributor authorD. L. O’Neal
    contributor authorS. Katipamula
    date accessioned2017-05-08T23:42:29Z
    date available2017-05-08T23:42:29Z
    date copyrightAugust, 1993
    date issued1993
    identifier issn0199-6231
    identifier otherJSEEDO-28246#176_1.pdf
    identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/112588
    description abstractA nondimensional cycling model for estimating the seasonal performance of conventional air conditioners and heat pumps was developed. Starting with a simple time-constant model of the startup of an air conditioner, a nondimensional time variable was developed which captures three important influences of on-off cycling performance degradation: response of the system, fraction on-time of the system, and cycling rate. Experimental data from three air conditioners and one heat pump provided excellent agreement with the model. The model should be applicable to any cooling technology that has similar on-off characteristics to conventional air conditioners and heat pumps.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleDevelopment of Nondimensional Cycling Model for Estimating the Seasonal Performance of Air Conditioners
    typeJournal Paper
    journal volume115
    journal issue3
    journal titleJournal of Solar Energy Engineering
    identifier doi10.1115/1.2930046
    journal fristpage176
    journal lastpage181
    identifier eissn1528-8986
    keywordsAir conditioners
    keywordsHeat pumps AND Cooling
    treeJournal of Solar Energy Engineering:;1993:;volume( 115 ):;issue: 003
    contenttypeFulltext