Show simple item record

contributor authorKatinas, Christopher;Reichardt, Thomas;d’Entremont, Brian;Ray, William;Willis, Michael;Kulp, Thomas
date accessioned2023-04-06T13:01:06Z
date available2023-04-06T13:01:06Z
date copyright10/14/2022 12:00:00 AM
date issued2022
identifier issn19485085
identifier othertsea_15_1_011013.pdf
identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4288929
description abstractMonitoring of cooling tower performance in a nuclear reactor facility is necessary to ensure safe operation; however, instrumentation for measuring performance characteristics can be difficult to install and may malfunction or break down over long duration experiments. This paper describes employing a thermodynamic approach to quantify cooling tower performance, the Merkel model, which requires only five parameters, namely, inlet water temperature, outlet water temperature, liquid mass flowrate, gas mass flowrate, and wet bulb temperature. Using this model, a general method to determine cooling tower operation for a nuclear reactor was developed in situations when neither the outlet water temperature nor gas mass flowrate are available, the former being a critical piece of information to bound the Merkel integral. Furthermore, when multiple cooling tower cells are used in parallel (as would be in the case of largescale cooling operations), only the average outlet temperature of the cooling system is used as feedback for fan speed control, increasing the difficulty of obtaining the outlet water temperature for each cell. To address these shortcomings, this paper describes a method to obtain individual cell outlet water temperatures for mechanical forcedair cooling towers via parametric analysis and optimization. In this method, the outlet water temperature for an individual cooling tower cell is acquired as a function of the liquidtogas ratio (L/G). Leveraging the tight tolerance on the average outlet water temperature, an error function is generated to describe the deviation of the parameterized L/G to the highly controlled average outlet temperature. The method was able to determine the gas flowrate at rated conditions to be within 3.9% from that obtained from the manufacturer’s specification, while the average error for the four individual cooling cell outlet water temperatures were 1.6 °C, −0.5 °C, −1.0 °C, and 0.3 °C.
publisherThe American Society of Mechanical Engineers (ASME)
titleCalculation of Nuclear Reactor Cooling Tower Performance With Limited Data Streams
typeJournal Paper
journal volume15
journal issue1
journal titleJournal of Thermal Science and Engineering Applications
identifier doi10.1115/1.4055746
journal fristpage11013
journal lastpage1101310
page10
treeJournal of Thermal Science and Engineering Applications:;2022:;volume( 015 ):;issue: 001
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record