Show simple item record

contributor authorMingsheng Liu
contributor authorDavid E. Claridge
date accessioned2017-05-09T00:00:47Z
date available2017-05-09T00:00:47Z
date copyrightAugust, 1999
date issued1999
identifier issn0199-6231
identifier otherJSEEDO-28285#171_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/122783
description abstractThis paper presents the physical models for the maximum potential thermal energy savings from optimizing the hot deck and cold deck reset schedules for dual duct variable air volume systems. The maximum potential savings can be determined by using these models combined with basic system operating parameters and bin data. The system performance can be evaluated by comparing the actual savings with the maximum potential savings. The energy savings from optimal cold deck and hot deck reset schedules in multi-zone buildings should be at least 75 percent of the maximum potential savings.
publisherThe American Society of Mechanical Engineers (ASME)
titleThe Maximum Potential Energy Savings from Optimizing Cold Deck and Hot Deck Reset Schedules for Dual Duct VAV Systems
typeJournal Paper
journal volume121
journal issue3
journal titleJournal of Solar Energy Engineering
identifier doi10.1115/1.2888429
journal fristpage171
journal lastpage175
identifier eissn1528-8986
keywordsPotential energy
keywordsDucts
keywordsStructures AND Thermal energy
treeJournal of Solar Energy Engineering:;1999:;volume( 121 ):;issue: 003
contenttypeFulltext