Show simple item record

contributor authorSrinivas Katipamula
contributor authorDennis L. O’Neal
date accessioned2017-05-08T23:36:27Z
date available2017-05-08T23:36:27Z
date copyrightNovember, 1991
date issued1991
identifier issn0199-6231
identifier otherJSEEDO-28232#264_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/109110
description abstractMuch of the seasonal cooling operation of the heat pump occurs at part-load conditions when the unit cycles on and off to meet the cooling load. The seasonal efficiency under part-load conditions of the heat pump is typically estimated from a laboratory measurement of the degradation coefficient (CD ) . Manufacturers are only required to estimate CD at a single test condition where the indoor coil performs sensible cooling only. The effects of transient dehumidification losses are not accounted in estimating the seasonal efficiency. In hot and humid climates, dehumidification performance of a heat pump is as important as the sensible cooling performance. Therefore, a series of tests were designed to quantify the part-load dehumidification characteristics of a three ton residential air-to-air heat pump. The tests include: cycling rates from 0.8 to 10 cycles per hour (cph), percent on-times of 20, 50, and 80 percent, indoor dry-bulb temperature between 22.2°C and 26.7°C, and indoor relative humidity between 20 to 67 percent. The outdoor conditions and the indoor air flow rate were constant for all test runs. All experiments were performed in psychometric chambers under controlled conditions. The dehumidification process started between 60 to 150 seconds after start-up depending on the test conditions. During start-up, the losses in the latent capacity were greater than the losses in the sensible capacity. The dehumidification response increased with indoor dry-bulb temperature at constant relative humidity and decreased with indoor temperature at constant dew-point temperature.
publisherThe American Society of Mechanical Engineers (ASME)
titleTransient Dehumidification Characteristics of a Heat Pump in Cooling Mode
typeJournal Paper
journal volume113
journal issue4
journal titleJournal of Solar Energy Engineering
identifier doi10.1115/1.2929972
journal fristpage264
journal lastpage271
identifier eissn1528-8986
keywordsCooling
keywordsDehumidification
keywordsHeat pumps
keywordsTemperature
keywordsStress
keywordsCycles
keywordsClimate AND Air flow
treeJournal of Solar Energy Engineering:;1991:;volume( 113 ):;issue: 004
contenttypeFulltext