    Structural Analysis and Control of a Model of Two-Site Electricity and Heat Supply

    Source: Journal of Dynamic Systems, Measurement, and Control:;2019:;volume( 141 ):;issue: 010::page 101004
    Author:
    Hoshino, Hikaru
    ,
    Susuki, Yoshihiko
    ,
    John Koo, T.
    ,
    Hikihara, Takashi
    DOI: 10.1115/1.4043703
    Publisher: American Society of Mechanical Engineers (ASME)
    Abstract: This paper introduces a control problem of regulation of energy flows in a two-site electricity and heat supply system, where two combined heat and power (CHP) plants are interconnected via electricity and heat flows. The control problem is motivated by recent development of fast operation of CHP plants to provide ancillary services of power system on the order of tens of seconds to minutes. Due to the physical constraint that the responses of the heat subsystem are not necessary as fast as those of the electric subsystem, the target controlled state is not represented by any isolated equilibrium point, implying that stability of the system is lost in the long-term sense on the order of hours. In this paper, we first prove in the context of nonlinear control theory that the state-space model of the two-site system is nonminimum phase due to nonexistence of isolated equilibrium points of the associated zero dynamics. Instead, we locate a one-dimensional (1D) invariant manifold that represents the target controlled flows completely. Then, by utilizing a virtual output under which the state-space model becomes minimum phase, we synthesize a controller that achieves not only the regulation of energy flows in the short-term regime but also stabilization of an equilibrium point in the long-term regime. Effectiveness of the synthesized controller is established with numerical simulations with a practical set of model parameters.
    • Download: (1.619Mb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Statistics

      Structural Analysis and Control of a Model of Two-Site Electricity and Heat Supply

    URI
    https://yetl.yabesh.ir/yetl1/handle/yetl/4258013
    Collections
    • Journal of Dynamic Systems, Measurement, and Control

    Show full item record

    contributor authorHoshino, Hikaru
    contributor authorSusuki, Yoshihiko
    contributor authorJohn Koo, T.
    contributor authorHikihara, Takashi
    date accessioned2019-09-18T09:01:37Z
    date available2019-09-18T09:01:37Z
    date copyright6/3/2019 12:00:00 AM
    date issued2019
    identifier issn0022-0434
    identifier otherds_141_10_101004
    identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4258013
    description abstractThis paper introduces a control problem of regulation of energy flows in a two-site electricity and heat supply system, where two combined heat and power (CHP) plants are interconnected via electricity and heat flows. The control problem is motivated by recent development of fast operation of CHP plants to provide ancillary services of power system on the order of tens of seconds to minutes. Due to the physical constraint that the responses of the heat subsystem are not necessary as fast as those of the electric subsystem, the target controlled state is not represented by any isolated equilibrium point, implying that stability of the system is lost in the long-term sense on the order of hours. In this paper, we first prove in the context of nonlinear control theory that the state-space model of the two-site system is nonminimum phase due to nonexistence of isolated equilibrium points of the associated zero dynamics. Instead, we locate a one-dimensional (1D) invariant manifold that represents the target controlled flows completely. Then, by utilizing a virtual output under which the state-space model becomes minimum phase, we synthesize a controller that achieves not only the regulation of energy flows in the short-term regime but also stabilization of an equilibrium point in the long-term regime. Effectiveness of the synthesized controller is established with numerical simulations with a practical set of model parameters.
    publisherAmerican Society of Mechanical Engineers (ASME)
    titleStructural Analysis and Control of a Model of Two-Site Electricity and Heat Supply
    typeJournal Paper
    journal volume141
    journal issue10
    journal titleJournal of Dynamic Systems, Measurement, and Control
    identifier doi10.1115/1.4043703
    journal fristpage101004
    journal lastpage101004-13
    treeJournal of Dynamic Systems, Measurement, and Control:;2019:;volume( 141 ):;issue: 010
    contenttypeFulltext
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian
     
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian