    Conditions for the Input-Output Relation of Perfect-Mixing Processes to be First Order With Application to Building Ventilation Systems

    Source: Journal of Dynamic Systems, Measurement, and Control:;1998:;volume( 120 ):;issue: 002::page 170
    Author:
    C. C. Federspiel
    DOI: 10.1115/1.2802406
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: Perfect-mixing models are commonly used for analyzing the performance of building ventilation systems. Recently, they have been used to estimate the strength of gas sources in buildings. However, buildings are generally partitioned in such a way that scalar first-order models are insufficient to completely describe the dynamic behavior of the gas transport in buildings. This paper addresses the question of when scalar, first-order differential equations are useful for describing the aggregate dynamical behavior of multi-variable perfect-mixing processes. Sufficient conditions for the input-output relation of a multi-variable perfect-mixing process to be a first-order differential equation are derived. The conditions are related to sensor location and system design. It is shown that the design condition is too restrictive to be widely applicable. Therefore, an alternative first-order relationship is derived by replacing the design condition with a leakage condition. The results enable the estimation of aggregate parameters of multi-zone ventilation systems from scalar, first-order differential equations, which substantially simplifies the estimation problem.
    keyword(s): Ventilation equipment , Design , Differential equations , Scalars , Structures , Sensors AND Leakage ,
    • Download: (687.9Kb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Statistics

      Conditions for the Input-Output Relation of Perfect-Mixing Processes to be First Order With Application to Building Ventilation Systems

    URI
    https://yetl.yabesh.ir/yetl1/handle/yetl/120184
    Collections
    • Journal of Dynamic Systems, Measurement, and Control

    Show full item record

    contributor authorC. C. Federspiel
    date accessioned2017-05-08T23:56:08Z
    date available2017-05-08T23:56:08Z
    date copyrightJune, 1998
    date issued1998
    identifier issn0022-0434
    identifier otherJDSMAA-26246#170_1.pdf
    identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/120184
    description abstractPerfect-mixing models are commonly used for analyzing the performance of building ventilation systems. Recently, they have been used to estimate the strength of gas sources in buildings. However, buildings are generally partitioned in such a way that scalar first-order models are insufficient to completely describe the dynamic behavior of the gas transport in buildings. This paper addresses the question of when scalar, first-order differential equations are useful for describing the aggregate dynamical behavior of multi-variable perfect-mixing processes. Sufficient conditions for the input-output relation of a multi-variable perfect-mixing process to be a first-order differential equation are derived. The conditions are related to sensor location and system design. It is shown that the design condition is too restrictive to be widely applicable. Therefore, an alternative first-order relationship is derived by replacing the design condition with a leakage condition. The results enable the estimation of aggregate parameters of multi-zone ventilation systems from scalar, first-order differential equations, which substantially simplifies the estimation problem.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleConditions for the Input-Output Relation of Perfect-Mixing Processes to be First Order With Application to Building Ventilation Systems
    typeJournal Paper
    journal volume120
    journal issue2
    journal titleJournal of Dynamic Systems, Measurement, and Control
    identifier doi10.1115/1.2802406
    journal fristpage170
    journal lastpage176
    identifier eissn1528-9028
    keywordsVentilation equipment
    keywordsDesign
    keywordsDifferential equations
    keywordsScalars
    keywordsStructures
    keywordsSensors AND Leakage
    treeJournal of Dynamic Systems, Measurement, and Control:;1998:;volume( 120 ):;issue: 002
    contenttypeFulltext