    Impact of Server Thermal Design on the Cooling Efficiency: Chassis Design

    Thumbnail
    View/Open
    ep_141_03_031004.pdf (8.548Mb)
    Date
    2019
    Author
    Khalili, Sadegh
    Alissa, Husam
    Nemati, Kourosh
    Seymour, Mark
    Curtis, Robert
    Moss, David
    Sammakia, Bahgat
    Metadata
    Show full item record
    Abstract
    There are various designs for segregating hot and cold air in data centers such as cold aisle containment (CAC), hot aisle containment (HAC), and chimney exhaust rack. These containment systems have different characteristics and impose various conditions on the information technology equipment (ITE). One common issue in HAC systems is a pressure build-up inside the HAC (known as backpressure). Backpressure also can be present in CAC systems in case of airflow imbalances. Hot air recirculation, limited cooling airflow rate in servers, and reversed flow through ITE with weaker fan systems (e.g., network switches) are some known consequences of backpressure. Currently, there is a lack of experimental data on the interdependency between overall performance of ITE and its internal design when backpressure is imposed on ITE. In this paper, three commercial 2-rack unit (RU) servers with different internal designs from various generations and performance levels are tested and analyzed under various environmental conditions. Smoke tests and thermal imaging are implemented to study the airflow patterns inside the tested equipment. In addition, the impact of hot air leakage into the servers through chassis perforations on the fan speed and the power consumption of the servers are studied. Furthermore, the cause of the discrepancy between measured inlet temperatures by the intelligent platform management interface (IPMI) and external sensors is investigated. It is found that arrangement of fans, segregation of space upstream and downstream of fans, leakage paths, the location of baseboard management controller (BMC) sensors, and the presence of backpressure can have a significant impact on ITE power and cooling efficiency.
    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/4257838
    Collections
    • Journal of Electronic Packaging

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV