Show simple item record

dc.contributor.authorDo Nhu C.;Simpson Angus R.;Deuerlein Jochen W.;Piller Olivier
dc.date.accessioned2019-02-26T07:35:51Z
dc.date.available2019-02-26T07:35:51Z
dc.date.issued2018
dc.identifier.other%28ASCE%29WR.1943-5452.0000958.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4248149
dc.description.abstractThe reliability of a water distribution system is highly dependent on the management of its pipeline network. A pipe or a portion of the network can be isolated for inspection, maintenance, and replacement by the installation of isolation valves along the pipelines. However, the presence of isolation valves may cause a large discrepancy in the hydraulic behavior between the real system and results from a simulation model if the statuses of some of the valves in the system are unknown. Possible problems related to these valves are missing valves in the model due to poor or nonexistent documentation, errors in data transfer, or valve mechanical failure. This paper introduces an innovative methodology for the identification of unknown partially/fully closed valves in a water distribution network. An optimization problem is formulated for the unknown valve issue and solved by application of three sequentially applied methods, which include a local sensitivity analysis, an application of genetic algorithms (GAs), and an application of the Levenberg-Marquardt algorithm. In the first method, the sensitivity of the flow rates and nodal heads at measurement locations with respect to the change in the minor losses of the valves is computed. This computation is used to identify the valves that are unable to be localized by the measurement data. The second method applies a genetic algorithm combined with an extended period simulation in order to preliminarily identify the locations of the partially/fully closed valves and their setting values, i.e., the degree of opening of the valve. Finally, the application of the Levenberg-Marquardt (LM) algorithm was implemented to correct the results from the GA model. Results and discussions from two case studies show that the proposed methodologies can solve real-world problems.
dc.publisherAmerican Society of Civil Engineers
dc.titleLocating Inadvertently Partially Closed Valves in Water Distribution Systems
dc.typeJournal Paper
dc.journal.volume144
dc.journal.issue8
dc.journal.titleJournal of Water Resources Planning and Management
dc.identifier.doi10.1061/(ASCE)WR.1943-5452.0000958
dc.page4018039
dc.treeJournal of Water Resources Planning and Management:;2018:;Volume ( 144 ):;issue: 008
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record