Variations of Stratification and Cooling Energy Performance According to Diffuser Condition in UFAD SystemSource: Journal of Energy Engineering:;2020:;Volume ( 146 ):;issue: 004DOI: 10.1061/(ASCE)EY.1943-7897.0000663Publisher: ASCE
Abstract: The underfloor air distribution (UFAD) system, which is a building energy-saving technology, is an air-conditioning system that enables maintenance of the indoor temperature with a relatively low supply air flow rate. UFAD has advantages compared to the conventional overhead system, which improves occupants’ comfort, health, and work efficiency, decreases life cycle cost, and improves indoor air quality, ventilation efficiency, and lay-out flexibility related to building services. Also, the floor height is reduced because a duct is unnecessary. The stratification of the UFAD system is a key factor to the system, which refers to the inconsistent vertical temperature distribution from the floor to the ceiling due to the buoyant effect of air. It plays a critical role in determining the thermal, ventilation, and energy performance. However, based on the comprehensive literature review, study on the stratification of UFAD is insufficient due to lack of understanding and actual measurement facilities related to UFAD. Therefore, this study, by using the EnergyPlus simulation and phi-gamma formula, aims to assess the stratification according to the variation of a diffuser condition. As a result, stratification of the perimeter zone was improved by diffuser condition but the energy savings was not noticeable. The floor area of the interior zone accounts for 75% of the total floor area but stratification of the interior zone was not nearly changed by diffuser condition. Also, as the stratification was improved, the wall convection heat gain increased in the interior zone. Therefore, it is considered that the cooling load was increased and the decrease of energy consumption is insignificant.
|
Collections
Show full item record
contributor author | Sang Hun Yeon | |
contributor author | Byeongho Yu | |
contributor author | Jong Man Lee | |
contributor author | Sung Lok Do | |
contributor author | Minjae Shin | |
contributor author | Kwang Ho Lee | |
date accessioned | 2022-01-30T19:34:00Z | |
date available | 2022-01-30T19:34:00Z | |
date issued | 2020 | |
identifier other | %28ASCE%29EY.1943-7897.0000663.pdf | |
identifier uri | http://yetl.yabesh.ir/yetl1/handle/yetl/4265556 | |
description abstract | The underfloor air distribution (UFAD) system, which is a building energy-saving technology, is an air-conditioning system that enables maintenance of the indoor temperature with a relatively low supply air flow rate. UFAD has advantages compared to the conventional overhead system, which improves occupants’ comfort, health, and work efficiency, decreases life cycle cost, and improves indoor air quality, ventilation efficiency, and lay-out flexibility related to building services. Also, the floor height is reduced because a duct is unnecessary. The stratification of the UFAD system is a key factor to the system, which refers to the inconsistent vertical temperature distribution from the floor to the ceiling due to the buoyant effect of air. It plays a critical role in determining the thermal, ventilation, and energy performance. However, based on the comprehensive literature review, study on the stratification of UFAD is insufficient due to lack of understanding and actual measurement facilities related to UFAD. Therefore, this study, by using the EnergyPlus simulation and phi-gamma formula, aims to assess the stratification according to the variation of a diffuser condition. As a result, stratification of the perimeter zone was improved by diffuser condition but the energy savings was not noticeable. The floor area of the interior zone accounts for 75% of the total floor area but stratification of the interior zone was not nearly changed by diffuser condition. Also, as the stratification was improved, the wall convection heat gain increased in the interior zone. Therefore, it is considered that the cooling load was increased and the decrease of energy consumption is insignificant. | |
publisher | ASCE | |
title | Variations of Stratification and Cooling Energy Performance According to Diffuser Condition in UFAD System | |
type | Journal Paper | |
journal volume | 146 | |
journal issue | 4 | |
journal title | Journal of Energy Engineering | |
identifier doi | 10.1061/(ASCE)EY.1943-7897.0000663 | |
page | 04020017 | |
tree | Journal of Energy Engineering:;2020:;Volume ( 146 ):;issue: 004 | |
contenttype | Fulltext |