    Vibrations Serviceability of a Medical Facility Floor for Sensitive Equipment Replacement: Evaluation with Sparse In Situ Data

    Source: Practice Periodical on Structural Design and Construction:;2019:;Volume ( 024 ):;issue: 001
    Author:
    Onur Avci; Ashish Bhargava; Yahia Al-Smadi; Jeremy Isenberg
    DOI: 10.1061/(ASCE)SC.1943-5576.0000404
    Publisher: American Society of Civil Engineers
    Abstract: Vibrations serviceability of building floors has been a growing concern over the years. For steel-framed systems, vibrations serviceability checks often govern the structural design. When the floor is carrying vibration-sensitive equipment, vibrations serviceability evaluation is more critical because the serviceability on the floor involves the use of expensive equipment generally related to human health (patient rooms, operating rooms, medical laboratories, etc.) This article summarizes a study in which a new (replacement) magnetic resonance imaging (MRI) unit with a weight of 8.6 t (19,000 lb) was to replace a heavier MRI unit weighing 37.2 t (82,000 lb) on an elevated floor of a medical facility. Although the dynamic characteristics of the floor would change with this drastic load difference on the bay, the vibration response of the floor for nearby footfall excitations was also expected to change. This brought up the question of whether the footfall-induced excitations would pass the maximum acceleration limit set by the manufacturer of the replacement MRI unit. The authors were provided with in situ vibration measurements collected when the old MRI unit was in place and were asked to decide if the footfall-induced excitations around the replacement unit would exceed its manufacturer criteria. Sparse in situ vibration measurements of the old MRI configuration were used to calibrate a detailed finite-element model that was later used to predict the footfall response for the replacement MRI unit configuration. The predicted accelerations were then compared with the manufacturer’s limiting accelerations for the replacement MRI unit. It was determined that the accelerations estimated for the replacement unit were not more than the manufacturer’s limiting criteria.
    • Download: (5.041Mb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Price: 5000 Rial
    • Statistics

      Vibrations Serviceability of a Medical Facility Floor for Sensitive Equipment Replacement: Evaluation with Sparse In Situ Data

    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/4255451
    Collections
    • Journal of Structural Design and Construction Practice

    Show full item record

    contributor authorOnur Avci; Ashish Bhargava; Yahia Al-Smadi; Jeremy Isenberg
    date accessioned2019-03-10T12:23:27Z
    date available2019-03-10T12:23:27Z
    date issued2019
    identifier other%28ASCE%29SC.1943-5576.0000404.pdf
    identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4255451
    description abstractVibrations serviceability of building floors has been a growing concern over the years. For steel-framed systems, vibrations serviceability checks often govern the structural design. When the floor is carrying vibration-sensitive equipment, vibrations serviceability evaluation is more critical because the serviceability on the floor involves the use of expensive equipment generally related to human health (patient rooms, operating rooms, medical laboratories, etc.) This article summarizes a study in which a new (replacement) magnetic resonance imaging (MRI) unit with a weight of 8.6 t (19,000 lb) was to replace a heavier MRI unit weighing 37.2 t (82,000 lb) on an elevated floor of a medical facility. Although the dynamic characteristics of the floor would change with this drastic load difference on the bay, the vibration response of the floor for nearby footfall excitations was also expected to change. This brought up the question of whether the footfall-induced excitations would pass the maximum acceleration limit set by the manufacturer of the replacement MRI unit. The authors were provided with in situ vibration measurements collected when the old MRI unit was in place and were asked to decide if the footfall-induced excitations around the replacement unit would exceed its manufacturer criteria. Sparse in situ vibration measurements of the old MRI configuration were used to calibrate a detailed finite-element model that was later used to predict the footfall response for the replacement MRI unit configuration. The predicted accelerations were then compared with the manufacturer’s limiting accelerations for the replacement MRI unit. It was determined that the accelerations estimated for the replacement unit were not more than the manufacturer’s limiting criteria.
    publisherAmerican Society of Civil Engineers
    titleVibrations Serviceability of a Medical Facility Floor for Sensitive Equipment Replacement: Evaluation with Sparse In Situ Data
    typeJournal Paper
    journal volume24
    journal issue1
    journal titlePractice Periodical on Structural Design and Construction
    identifier doi10.1061/(ASCE)SC.1943-5576.0000404
    page05018006
    treePractice Periodical on Structural Design and Construction:;2019:;Volume ( 024 ):;issue: 001
    contenttypeFulltext