description abstractSelection of fouling factors is somewhat arbitrary in heat exchanger networks (HENs) synthesis. Fouling factors were reconsidered in this article for heat exchanger networks design. An objective function based on exergoeconomic analysis was introduced to assess optimal less conservative fouling factors. The objective took account of exergy consumption expense and heat exchanger capital cost at the same time. The exergy consumption of heat transfer in HENs was calculated using subsection integral on balanced composite curves. The proposed method was applied to an industrial case. Numerical results indicated that the optimal less conservative fouling factors were 80% of the original values and the heat transfer area of the system saved 350 m2 compared with root design. So it is necessary to reconsider the values of fouling factors for HENs design and that exergoeconomic analysis is useful in determining the optimal less conservative fouling factors.
publisherThe American Society of Mechanical Engineers (ASME)
titleExergy Study of Fouling Factors in Heat Exchanger Networks
typeJournal Paper
journal volume132
journal issue1
journal titleJournal of Heat Transfer
identifier doi10.1115/1.3194766
journal fristpage11802
identifier eissn1528-8943
keywordsHeat transfer
keywordsExergy
keywordsHeat exchangers AND Networks
treeJournal of Heat Transfer:;2010:;volume( 132 ):;issue: 001
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record