Show simple item record

contributor authorAmip J. Shah
contributor authorCullen E. Bash
contributor authorChandrakant D. Patel
contributor authorVan P. Carey
date accessioned2017-05-09T00:29:13Z
date available2017-05-09T00:29:13Z
date copyrightFebruary, 2008
date issued2008
identifier issn0022-1481
identifier otherJHTRAO-27831#021401_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/138604
description abstractThe modeling of recirculation patterns in air-cooled data centers is of interest to ensure adequate thermal management of computer racks at increased heat densities. Most metrics that describe recirculation are based exclusively on temperature inside the data center, and therefore fail to provide adequate information regarding the energy efficiency of the thermal infrastructure. This paper addresses this limitation through an exergy analysis of the data center thermal management system. The approach recognizes that the mixing of hot and cold streams in the data center airspace is an irreversible process and must therefore lead to a loss of exergy. Experimental validation in a test data center confirms that such an exergy-based characterization in the cold aisle reflects the same recirculation trends as suggested by traditional temperature-based metrics. Further, by extending the exergy-based model to include irreversibilities from other components of the thermal architecture, it becomes possible to quantify the amount of available energy supplied to the cooling system that is being utilized for thermal management purposes. The energy efficiency of the entire data center cooling system can then be collapsed into the single metric of net exergy loss. When evaluated against a ground state of the external ambience, this metric enables an estimate of how much of the energy emitted into the environment could potentially be harnessed in the form of useful work. Thus, this paper successfully demonstrates that the proposed exergy-based approach can provide a foundation upon which the data center cooling system can be simultaneously evaluated for thermal manageability and energy efficiency.
publisherThe American Society of Mechanical Engineers (ASME)
titleExergy Analysis of Data Center Thermal Management Systems
typeJournal Paper
journal volume130
journal issue2
journal titleJournal of Heat Transfer
identifier doi10.1115/1.2787024
journal fristpage21401
identifier eissn1528-8943
keywordsTemperature
keywordsExergy
keywordsData centers
keywordsThermal management AND Heat
treeJournal of Heat Transfer:;2008:;volume( 130 ):;issue: 002
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record