Show simple item record

contributor authorM. Kanoğlu
contributor authorY. A. Çengel
contributor authorR. H. Turner
date accessioned2017-05-08T23:56:25Z
date available2017-05-08T23:56:25Z
date copyrightJune, 1998
date issued1998
identifier issn0195-0738
identifier otherJERTD2-26476#179_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/120334
description abstractGeothermal energy has been used for power generation, space and process heating, and to a lesser extent, space cooling. However, it is rarely used for cogeneration. This paper shows how a district heating/cooling system can be incorporated into an existing geothermal power plant to make the best use of extracted hot brine. In the power plant analysis, exergy destruction throughout the plant is quantified and illustrated using an exergy cascade. The primary source of exergy destruction in the plant is determined to be the reinjection of used brine into the ground, which accounts for 48.1 percent of the total exergy destruction. The overall first and the second law efficiencies of the plant are calculated to be 5.6 and 28.3 percent, respectively, based on the exergy of the geothermal fluid at downwell, and 5.7 and 28.6 percent, respectively, based on the exergy of the geothermal fluid at wellhead. A binary system is considered for the heating/cooling district to avoid corrosion and scaling problems. The heating system, as designed, has the capability to meet the entire needs of the Reno Industrial Park under peak load conditions, and has 30 percent reserve for future expansion. An absorption system will be used for the cooling of the intended 40 percent floor space of the industrial park. An economic analysis shows that the incorporation of the district heating/cooling system with 2,785,000 m2 of floor space connected to the geothermal grid appears to be feasible, and financially very attractive. Further, using the returning freshwater from the district heating/cooling system for partial cooling of the binary fluid of the power plant can save up to 15 percent of the fan work.
publisherThe American Society of Mechanical Engineers (ASME)
titleIncorporating a District Heating/Cooling System Into an Existing Geothermal Power Plant
typeJournal Paper
journal volume120
journal issue2
journal titleJournal of Energy Resources Technology
identifier doi10.1115/1.2795031
journal fristpage179
journal lastpage184
identifier eissn1528-8994
keywordsCentral heating
keywordsCooling systems
keywordsGeothermal power stations
keywordsExergy
keywordsCooling
keywordsFluids
keywordsGeothermal engineering
keywordsIndustrial plants
keywordsHeating
keywordsPower stations
keywordsCombined heat and power
keywordsEconomic analysis
keywordsElectric power generation
keywordsGeothermal power
keywordsCorrosion
keywordsEnergy generation
keywordsPeak load
keywordsAbsorption AND Cascades (Fluid dynamics)
treeJournal of Energy Resources Technology:;1998:;volume( 120 ):;issue: 002
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record