Show simple item record

contributor authorS. Z. Wu
contributor authorD. N. Wormley
contributor authorD. Rowell
contributor authorP. Griffith
date accessioned2017-05-08T23:19:47Z
date available2017-05-08T23:19:47Z
date copyrightDecember, 1985
date issued1985
identifier issn0022-0434
identifier otherJDSMAA-26089#267_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/99574
description abstractAn evaluation of systems for control of fossil fuel power plant boiler and stack implosions has been performed using computer simulation techniques described in a companion paper. The simulations have shown that forced and induced draft fan control systems and induced draft fan bypass systems reduce the furnace pressure excursions significantly following a main fuel trip. The limitations of these systems are associated with actuator range and response time and stack pressure excursions during control actions. Preliminary study suggests that an alternative control solution may be achieved by discharging steam into the furnace after a fuel trip.
publisherThe American Society of Mechanical Engineers (ASME)
titleBoiler Implosion Control in Fossil Fuel Power Plants
typeJournal Paper
journal volume107
journal issue4
journal titleJournal of Dynamic Systems, Measurement, and Control
identifier doi10.1115/1.3140734
journal fristpage267
journal lastpage269
identifier eissn1528-9028
treeJournal of Dynamic Systems, Measurement, and Control:;1985:;volume( 107 ):;issue: 004
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record