    Thermal Design and Performance Modeling of a High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center

    Source: Journal of Electronic Packaging:;2026:;volume( 148 ):;issue:002::page 1440
    Author:
    Tano, Ines-Noelly
    ,
    Rasouli, Erfan
    ,
    Narayanan, Vinod
    DOI: 10.1115/1.4071752
    Publisher: The American Society of Mechanical Engineers (ASME)
    Abstract: Abstract. Holistic design of a modular energy-efficient edge datacenter with a compute density of 20 kW/m3 is presented. The datacenter uses a single chiller-less liquid loop to extract heat from server components and reject it to the ambient using a mixture of 25% propylene glycol and water. Heat is extracted from the chips using a multiple unit-cell shedding enhanced (MUSE) cold plate and rejected to the ambient air using a counterflow microchannel polymer heat exchanger (MPHX) dry cooler. The MUSE cold plate consists of a manifold to split flow into parallel paths and a large aspect ratio (7.3:1) microscale pin fin heat sink fabricated using electrochemical additive manufacturing. The counterflow MPHX dry cooler design can provide higher effectiveness than metallic finned tube heat exchangers for identical air side pressure drop. Experiments of the cold plate and MPHX components are presented, and a system model of the cooling loop is developed. At an outdoor temperature of 40 °C, baseline results indicate that optimized liquid and fan flow rates reduce cooling power to 2.1% of compute power for a graphical processing unit (GPU) case temperature of 75 °C and heat flux of 74 W/cm2. Sensitivity studies are performed to assess the impact of improvements in thermal interface material, cold plate convective resistance, and dry cooler air-side heat transfer coefficient on system performance. Results show that, for this heat flux, the thermal interface material (TIM) and dry cooler have the largest impact on the system, with the best-case cooling power being under 1% of compute power.
    • Download: (4.798Mb)
    • Show Full MetaData Hide Full MetaData
    • Get RIS
    • Item Order
    • Go To Publisher
    • Statistics

      Thermal Design and Performance Modeling of a High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center

    URI
    https://yetl.yabesh.ir/yetl1/handle/yetl/4315877
    Collections
    • Journal of Electronic Packaging

    Show full item record

    contributor authorTano, Ines-Noelly
    contributor authorRasouli, Erfan
    contributor authorNarayanan, Vinod
    date accessioned2026-08-23T07:58:15Z
    date available2026-08-23T07:58:15Z
    date copyright2026/06/01
    date issued2026
    identifier issn1043-7398
    identifier otherep-25-1142.pdf
    identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4315877
    description abstractAbstract. Holistic design of a modular energy-efficient edge datacenter with a compute density of 20 kW/m3 is presented. The datacenter uses a single chiller-less liquid loop to extract heat from server components and reject it to the ambient using a mixture of 25% propylene glycol and water. Heat is extracted from the chips using a multiple unit-cell shedding enhanced (MUSE) cold plate and rejected to the ambient air using a counterflow microchannel polymer heat exchanger (MPHX) dry cooler. The MUSE cold plate consists of a manifold to split flow into parallel paths and a large aspect ratio (7.3:1) microscale pin fin heat sink fabricated using electrochemical additive manufacturing. The counterflow MPHX dry cooler design can provide higher effectiveness than metallic finned tube heat exchangers for identical air side pressure drop. Experiments of the cold plate and MPHX components are presented, and a system model of the cooling loop is developed. At an outdoor temperature of 40 °C, baseline results indicate that optimized liquid and fan flow rates reduce cooling power to 2.1% of compute power for a graphical processing unit (GPU) case temperature of 75 °C and heat flux of 74 W/cm2. Sensitivity studies are performed to assess the impact of improvements in thermal interface material, cold plate convective resistance, and dry cooler air-side heat transfer coefficient on system performance. Results show that, for this heat flux, the thermal interface material (TIM) and dry cooler have the largest impact on the system, with the best-case cooling power being under 1% of compute power.
    publisherThe American Society of Mechanical Engineers (ASME)
    titleThermal Design and Performance Modeling of a High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center
    typeJournal Paper
    journal volume148
    journal issue2
    journal titleJournal of Electronic Packaging
    identifier doi10.1115/1.4071752
    journal fristpage1440
    journal lastpage1452
    page13
    treeJournal of Electronic Packaging:;2026:;volume( 148 ):;issue:002
    contenttypeFulltext
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian
     
    DSpace software copyright © 2002-2015  DuraSpace
    نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
    yabeshDSpacePersian