Numerical Investigation of Cross-Flow Water Cooling TowersSource: Journal of Thermal Science and Engineering Applications:;2023:;volume( 015 ):;issue: 007::page 71010-1DOI: 10.1115/1.4062356Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: In this study, thermal performance of the forced cross-flow water cooling tower is numerically investigated by using the commercial computational fluid dynamics software ansys-cfx. The temperature variation between inlet and outlet of the water, namely, process water temperature, is the main extracted result of simulations. Additionally, the cooling range (CR) that is the difference between inlet water temperature and outlet water temperature is the second representative result of the analysis. The effect of air velocity (Va), water droplet diameter (dw), and water temperature at the inlet of tower (Tw) are the variables that are considered to be the effective design parameters on the process temperature of the water. The process water temperature decreases, but the cooling range increases when the air velocity increases. When the inlet water temperature increases, the process water temperature and the cooling range also increase. On the other hand, the process water temperature decreases with the decreasing diameter of water droplets.
|
Show full item record
| contributor author | Can, Omer F. | |
| contributor author | Alabbas, Muhammed | |
| date accessioned | 2023-11-29T19:43:58Z | |
| date available | 2023-11-29T19:43:58Z | |
| date copyright | 5/18/2023 12:00:00 AM | |
| date issued | 5/18/2023 12:00:00 AM | |
| date issued | 2023-05-18 | |
| identifier issn | 1948-5085 | |
| identifier other | tsea_15_7_071010.pdf | |
| identifier uri | http://yetl.yabesh.ir/yetl1/handle/yetl/4294987 | |
| description abstract | In this study, thermal performance of the forced cross-flow water cooling tower is numerically investigated by using the commercial computational fluid dynamics software ansys-cfx. The temperature variation between inlet and outlet of the water, namely, process water temperature, is the main extracted result of simulations. Additionally, the cooling range (CR) that is the difference between inlet water temperature and outlet water temperature is the second representative result of the analysis. The effect of air velocity (Va), water droplet diameter (dw), and water temperature at the inlet of tower (Tw) are the variables that are considered to be the effective design parameters on the process temperature of the water. The process water temperature decreases, but the cooling range increases when the air velocity increases. When the inlet water temperature increases, the process water temperature and the cooling range also increase. On the other hand, the process water temperature decreases with the decreasing diameter of water droplets. | |
| publisher | The American Society of Mechanical Engineers (ASME) | |
| title | Numerical Investigation of Cross-Flow Water Cooling Towers | |
| type | Journal Paper | |
| journal volume | 15 | |
| journal issue | 7 | |
| journal title | Journal of Thermal Science and Engineering Applications | |
| identifier doi | 10.1115/1.4062356 | |
| journal fristpage | 71010-1 | |
| journal lastpage | 71010-7 | |
| page | 7 | |
| tree | Journal of Thermal Science and Engineering Applications:;2023:;volume( 015 ):;issue: 007 | |
| contenttype | Fulltext |