Assessment of Two Phase Cooling of Power Electronics Using Roll Bonded CondensersSource: Journal of Thermal Science and Engineering Applications:;2015:;volume( 007 ):;issue: 001::page 11002DOI: 10.1115/1.4028346Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: Twophase thermosyphons with condensers from rollbonded panels, short “rollbond thermosiphons,†are attractive for powerelectronics cooling. Using simulations, the performance of rollbond thermosyphons and classical heat sinks is compared. The rollbond thermosyphons are advantageous in terms of tradeoff between thermal resistance, cooler volume or mass, and soundpower level. Under forced convection, where airside heattransfer coefficients are comparatively high, the classical heat sink suffers from low fin efficiency and limited heat spreading. By increasing the number of panels, the rollbond thermosyphon enables low thermal resistances that cannot be practically reached with classical heat sinks. For free air convection, the rollbond thermosyphon allows a significant reduction of thermal resistance and cooler mass.
|
Show full item record
| contributor author | Gradinger, Thomas B. | |
| contributor author | Agostini, Francesco | |
| date accessioned | 2017-05-09T01:23:41Z | |
| date available | 2017-05-09T01:23:41Z | |
| date issued | 2015 | |
| identifier issn | 1948-5085 | |
| identifier other | tsea_007_01_011002.pdf | |
| identifier uri | http://yetl.yabesh.ir/yetl/handle/yetl/159676 | |
| description abstract | Twophase thermosyphons with condensers from rollbonded panels, short “rollbond thermosiphons,†are attractive for powerelectronics cooling. Using simulations, the performance of rollbond thermosyphons and classical heat sinks is compared. The rollbond thermosyphons are advantageous in terms of tradeoff between thermal resistance, cooler volume or mass, and soundpower level. Under forced convection, where airside heattransfer coefficients are comparatively high, the classical heat sink suffers from low fin efficiency and limited heat spreading. By increasing the number of panels, the rollbond thermosyphon enables low thermal resistances that cannot be practically reached with classical heat sinks. For free air convection, the rollbond thermosyphon allows a significant reduction of thermal resistance and cooler mass. | |
| publisher | The American Society of Mechanical Engineers (ASME) | |
| title | Assessment of Two Phase Cooling of Power Electronics Using Roll Bonded Condensers | |
| type | Journal Paper | |
| journal volume | 7 | |
| journal issue | 1 | |
| journal title | Journal of Thermal Science and Engineering Applications | |
| identifier doi | 10.1115/1.4028346 | |
| journal fristpage | 11002 | |
| journal lastpage | 11002 | |
| identifier eissn | 1948-5093 | |
| tree | Journal of Thermal Science and Engineering Applications:;2015:;volume( 007 ):;issue: 001 | |
| contenttype | Fulltext |