Performance of a Residential-Sized GAX Absorption ChillerSource: Journal of Energy Resources Technology:;2001:;volume( 123 ):;issue: 003::page 236Author:Douglas K. Priedeman
,
Michael A. Garrabrant
,
James A. Mathias
,
Roger E. Stout
,
Richard N. Christensen
DOI: 10.1115/1.1385519Publisher: The American Society of Mechanical Engineers (ASME)
Abstract: This research effort involved experimentally testing an advanced-cycle, ammonia-water absorption chiller with a cooling capacity of 17.6 kW (5 refrigeration tons (RT)). The system was a generator-absorber heat exchange (GAX) cycle and was sized for residential and light commercial use, where very little absorption equipment is currently used. The components of the cycle were assembled with instrumentation, including flow meters, pressure transducers, and thermocouples. The findings of the research were cycle cooling load and coefficient of performance (COP), as well as many component heat duties and working fluid state points throughout the cycle. The COP of the chiller at essentially full load was measured at 0.68. A simulation of the GAX cycle was performed with a computer program that predicted the heat duties of each component and the cooling load of the cycle. The simulation of the GAX cycle and experimental testing compared closely. Existing market research shows that significant business opportunities exist for a GAX heat pump or chiller with a cooling COP of 0.70 or greater. The work performed in this study consisted of testing a GAX cycle with a COP that approached the target value of 0.70 and identified improvements that must be made to reach the target COP value.
keyword(s): Heat , Temperature , Cooling , Absorption , Stress , Design , Cycles , Generators , Water , Heat pumps , Thermocouples , Pressure , Refrigeration AND Fluids ,
|
Collections
Show full item record
| contributor author | Douglas K. Priedeman | |
| contributor author | Michael A. Garrabrant | |
| contributor author | James A. Mathias | |
| contributor author | Roger E. Stout | |
| contributor author | Richard N. Christensen | |
| date accessioned | 2017-05-09T00:04:40Z | |
| date available | 2017-05-09T00:04:40Z | |
| date copyright | September, 2001 | |
| date issued | 2001 | |
| identifier issn | 0195-0738 | |
| identifier other | JERTD2-26496#236_1.pdf | |
| identifier uri | http://yetl.yabesh.ir/yetl/handle/yetl/125092 | |
| description abstract | This research effort involved experimentally testing an advanced-cycle, ammonia-water absorption chiller with a cooling capacity of 17.6 kW (5 refrigeration tons (RT)). The system was a generator-absorber heat exchange (GAX) cycle and was sized for residential and light commercial use, where very little absorption equipment is currently used. The components of the cycle were assembled with instrumentation, including flow meters, pressure transducers, and thermocouples. The findings of the research were cycle cooling load and coefficient of performance (COP), as well as many component heat duties and working fluid state points throughout the cycle. The COP of the chiller at essentially full load was measured at 0.68. A simulation of the GAX cycle was performed with a computer program that predicted the heat duties of each component and the cooling load of the cycle. The simulation of the GAX cycle and experimental testing compared closely. Existing market research shows that significant business opportunities exist for a GAX heat pump or chiller with a cooling COP of 0.70 or greater. The work performed in this study consisted of testing a GAX cycle with a COP that approached the target value of 0.70 and identified improvements that must be made to reach the target COP value. | |
| publisher | The American Society of Mechanical Engineers (ASME) | |
| title | Performance of a Residential-Sized GAX Absorption Chiller | |
| type | Journal Paper | |
| journal volume | 123 | |
| journal issue | 3 | |
| journal title | Journal of Energy Resources Technology | |
| identifier doi | 10.1115/1.1385519 | |
| journal fristpage | 236 | |
| journal lastpage | 241 | |
| identifier eissn | 1528-8994 | |
| keywords | Heat | |
| keywords | Temperature | |
| keywords | Cooling | |
| keywords | Absorption | |
| keywords | Stress | |
| keywords | Design | |
| keywords | Cycles | |
| keywords | Generators | |
| keywords | Water | |
| keywords | Heat pumps | |
| keywords | Thermocouples | |
| keywords | Pressure | |
| keywords | Refrigeration AND Fluids | |
| tree | Journal of Energy Resources Technology:;2001:;volume( 123 ):;issue: 003 | |
| contenttype | Fulltext |