Show simple item record

dc.contributor.authorSiavash Soroushian
dc.contributor.authorArash E. Zaghi
dc.contributor.authorE. “Manos” Maragakis
dc.contributor.authorAlicia Echevarria
dc.contributor.authorYuan Tian
dc.contributor.authorAndre Filiatrault
dc.date.accessioned2017-05-08T22:12:09Z
dc.date.available2017-05-08T22:12:09Z
dc.date.copyrightJune 2015
dc.date.issued2015
dc.identifier.other39835209.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/73409
dc.description.abstractA comprehensive analytical model is developed for a pressurized fire sprinkler piping system of a hospital building. A suite of ninety-six artificial triaxial floor acceleration histories is used to generate seismic fragility parameters of the sprinkler piping system. The analytical model accounts for the inelastic behavior of braces, hangers, and wire restrainers. It incorporates an experimentally validated hysteresis model developed, as part of this study, for the moment-rotation relationship of grooved fitted joints. Component fragility parameters were obtained for lateral restrainers, hangers, and pipe joints. Three system-level damage states were defined based on the level of functionality of fire sprinkler systems and severity of leakage after a seismic event and a joint probabilistic model were utilized to obtain system-level fragility parameters. Finally, the seismic fragility of fire sprinkler systems with grooved fit joints is compared to that of a piping system with threaded joints.
dc.publisherAmerican Society of Civil Engineers
dc.titleSeismic Fragility Study of Fire Sprinkler Piping Systems with Grooved Fit Joints
dc.typeJournal Paper
dc.journal.volume141
dc.journal.issue6
dc.journal.titleJournal of Structural Engineering
dc.identifier.doi10.1061/(ASCE)ST.1943-541X.0001122
dc.treeJournal of Structural Engineering:;2015:;Volume ( 141 ):;issue: 006
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record