dc.description.abstractStructural fire endurance experiments were conducted on full-scale cellular glass fiber-reinforced (GFRP) columns under axial compression and subjected to ISO834 fire exposure from one side. Unprotected columns can resist fire for more than 30 min, which is sufficient for occupants to be evacuated from smaller buildings. The closed cellular cross-section prevented the rapid heating of the webs, which could therefore continue stabilizing the face sheet on the cold side against buckling. Water cooling was proven to offer an effective active fire-protection system. The structural function of the column could be maintained for two hours. Previously developed models were capable of accurately predicting the time-dependent temperature responses, modulus degradation, and time to failure.
dc.publisherAmerican Society of Civil Engineers
dc.titleFire Performance of Water-Cooled GFRP Columns. I: Fire Endurance Investigation
dc.typeJournal Paper
dc.journal.volume15
dc.journal.issue3
dc.journal.titleJournal of Composites for Construction
dc.identifier.doi10.1061/(ASCE)CC.1943-5614.0000160
dc.treeJournal of Composites for Construction:;2011:;Volume ( 015 ):;issue: 003
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record