Airtightness Testing of Two- and Three-Unit Buildings with a Single Fan
Abstract
This paper presents a method for the field measurement of airtightness for two- and three-unit buildings using only one fan pressurization system, commonly referred to as a blower door. The main advantage of this single-fan method is its lower equipment and labor cost as compared with multiple-fan methods. Results from consecutive tests in the individual units are used to prepare a set of simultaneous equations for airflow, allowing for the calculation of the air leakage characteristics of both the interior partitions and the exterior envelope on a unit-per-unit basis. Tests were performed on four buildings using the single-fan method and were compared with those obtained with a two-fan method. Test results indicate that the single-fan method may be of value as an inexpensive method of estimating the airtightness of two- and three-unit residential buildings.