• Login
    View Item 
    •   DSpace Home
    • ASME
    • ASME Journal of Heat and Mass Transfer
    • View Item
    •   DSpace Home
    • ASME
    • ASME Journal of Heat and Mass Transfer
    • View Item
    JavaScript is disabled for your browser. Some features of this site may not work without it.

    Performance Evaluation of Boiling Chamber With Microchannel Chip and Taper Microgap

    Thumbnail
    View/Open
    ht-25-1085.pdf (1.641Mb)
    Date
    2025
    Author
    Mustafa, Nooruldeen E.
    Kandlikar, Satish G.
    Metadata
    Show full item record
    Abstract
    Abstract. The increasing trend of power densities in high-performance computing, driven by artificial intelligence, machine learning, and cloud computing, necessitates advanced thermal management solutions to maintain operational stability and energy efficiency. This study examines the effectiveness of cooling a 1.5 U simulated copper microchannel chip compared to a plain chip. Both chip types were tested with and without configurations for dual taper microgaps to enhance the heat transfer performance of a boiling chamber (BC). Experimental investigation was conducted using 500 μm wide × 400 μm deep microchannels separated by 200 μm fins. Varying inlet gaps (0.5–4 mm) and taper lengths (8.25 mm and 16.5 mm) with a taper angle of 3 deg were employed in dual taper configuration. Their impact on critical heat flux (CHF) and subcooled boiling dynamics was investigated. Microchannels provided considerable performance enhancement over a plain surface with or without the dual taper microgap. The findings demonstrate that smaller inlet gaps (0.5–1 mm) and longer taper lengths (16.5 mm, with central liquid inlet) significantly enhance nucleate boiling. These configurations improve vapor escape and delay CHF through subcooled boiling and submerged condensation. However, a lower CHF was noted due to vapor agglomeration within the microgap. The 80% fill ratio microchannel chip exhibited the highest CHF as subcooled boiling increased liquid replenishment and prevented vapor stagnation. Similarly, lower coolant temperatures (20–30 °C) enhanced boiling performance, where submerged condensation accelerated bubble collapse and improved heat dissipation efficiency in lower surface temperatures.
    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/4316173
    Collections
    • ASME Journal of Heat and Mass Transfer

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV