Show simple item record

dc.contributor.authorB. Li
dc.contributor.authorP. Wang
dc.contributor.authorZ. Zhu
dc.contributor.authorZ. Li
dc.contributor.authorY. Xiao
dc.date.accessioned2024-12-24T09:58:20Z
dc.date.available2024-12-24T09:58:20Z
dc.date.copyright8/1/2024 12:00:00 AM
dc.date.issued2024
dc.identifier.otherJPCFEV.CFENG-4662.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4298052
dc.description.abstractMultistory industrial buildings have become prevalent in sectors such as electronics, machinery, pharmaceuticals, and textiles due to limited space in urban environment. There is usually a strict requirement of machine operation on the building vibration, so that it becomes relevant to quantify the structural dynamical characteristics, e.g., natural frequencies, damping ratios, and mode shapes. This paper presents a multisetup ambient vibration test and retest conducted in a multistory industrial building located in Haining, China, using eight triaxial accelerometers to cover 36 measurement locations in six setups during normal operations and shutdown condition. These tests followed a nearly identical test configuration with minor local discrepancies. To obtain the primary modal parameters of the structure, a Bayesian multisetup modal identification algorithm is adopted, followed with a detailed analysis of the results. Furthermore, the floor serviceability is investigated, primarily focusing on worker comfort. The study reveals several interesting phenomena, such as the impact of structural expansion joints and sensor synchronization on the identification results. This study serves as a demonstrative effort in examining the dynamic characteristics of multistory industrial buildings. It provides insight into evaluating the dynamic characteristics with limited sensors and abnormal identification results.
dc.publisherAmerican Society of Civil Engineers
dc.titleAmbient Vibration Test and Retest of a Multistory Factory Building
dc.typeJournal Article
dc.journal.volume38
dc.journal.issue4
dc.journal.titleJournal of Performance of Constructed Facilities
dc.identifier.doi10.1061/JPCFEV.CFENG-4662
dc.journal.fristpage04024021-1
dc.journal.lastpage04024021-13
dc.page13
dc.treeJournal of Performance of Constructed Facilities:;2024:;Volume ( 038 ):;issue: 004
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record