    Supervisory Control and Distributed Optimization of Building Energy Systems

    Thumbnail
    View/Open
    ds_142_10_101007.pdf (1.656Mb)
    Date
    2020
    Author
    Jiang, Zhanhong
    Chinde, Venkatesh
    Kohl, Adam
    Kelkar, Atul G.
    Sarkar, Soumik
    Metadata
    Show full item record
    Abstract
    Energy consumption in commercial buildings is significantly affected by the performance of heating, ventilation, and air-conditioning (HVAC) systems, which are traditionally operated using centralized controllers. HVAC control requires adjusting multiple setpoints such as chilled water temperatures and supply air temperature (SAT). Supervisory control framework in a distributed setting enables optimal HVAC operation and provides scalable solutions for optimizing energy across several scales from homes to regional areas. This paper proposes a distributed optimization framework for achieving energy efficiency in large-scale building energy systems. It is highly desirable to have building management systems that are scalable, robust, flexible, and are low cost. For addressing the scalability and flexibility, a modular problem formulation is established that decouples the distributed optimization level from local thermal zone modeling level. We leverage a recently developed generalized gossip algorithm for robust distributed optimization. The supervisory controller aims at minimizing the energy input considering occupant comfort. For validating the proposed scheme, a numerical case study based on a physical testbed in the Iowa Energy Center is presented. We show that the distributed optimization methodology outperforms the typical baseline strategy, which is a rule-based controller to set a constant supply air temperature. This paper also incorporates a software architecture based on the volttron platform, developed by the Pacific Northwest National Laboratory (PNNL), for practical implementation of the proposed framework via the BACnet system. The experimental results show that the supervisory control framework proposed in this paper can save energy by approximately 11%.
    URI
    http://yetl.yabesh.ir/yetl1/handle/yetl/4274553
    Collections
    • Journal of Dynamic Systems, Measurement, and Control

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV