Show simple item record

dc.contributor.authorGagnon, Lauren
dc.contributor.authorHelmns, Dre
dc.contributor.authorCarey, Van P.
dc.date.accessioned2022-02-04T14:51:07Z
dc.date.available2022-02-04T14:51:07Z
dc.date.copyright2020/04/10/
dc.date.issued2020
dc.identifier.issn0022-1481
dc.identifier.otherht_142_05_052905.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4274514
dc.description.abstractThis study links a model of thermal energy storage (TES) performance to a subsystem model with heat exchangers that cool down the storage at night; this cool storage is used to precool the air flow for a power plant air-cooled condenser during peak day temperatures. The subsystem model is also computationally linked to a model of Rankine cycle power plant performance to predict additional power the plant could generate due to the additional cooling. The model was used to explore the effects of varying phase change material (PCM) melt temperature and the energy input and rejection control settings with the goal of maximizing efficiency for a 50 MW power plant operating in the desert regions of Nevada for an average summer day. The results suggest that the kWh output of the modeled plant can be increased by up to 3.25% during the heat input/cold extraction period, and a cost analysis estimates that the TES system has the potential to provide additional revenue of up to $686,000 per year, depending on electricity cost and parameter choices.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleMultiscale Modeling of Power Plant Performance Enhancement Utilizing Asynchronous Cooling With Thermal Energy Storage
dc.typeJournal Paper
dc.journal.volume142
dc.journal.issue5
dc.journal.titleJournal of Heat Transfer
dc.identifier.doi10.1115/1.4046773
dc.page52905
dc.treeJournal of Heat Transfer:;2020:;volume( 142 ):;issue: 005
dc.contenttypeFulltext