Show simple item record

dc.contributor.authorZhiqiang Zhang
dc.contributor.authorDahai Wang
dc.contributor.authorTao Wang
dc.contributor.authorZechuan Yu
dc.contributor.authorZenghao Huang
dc.contributor.authorDonghong Zhang
dc.date.accessioned2022-01-30T22:37:32Z
dc.date.available2022-01-30T22:37:32Z
dc.date.issued1/1/2021
dc.identifier.other(ASCE)AS.1943-5525.0001223.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4269293
dc.description.abstractAn overhead transmission line system is a typical wind-sensitive structure with high flexibility, light weight, and low structural damping. Wind-induced dynamic reaction of the transmission line system is a determining factor in structural design of the supporting tower. In this study, we employ a closed-form solution and a series of wind tunnel tests to investigate three-dimensional dynamic reaction of transmission lines bundled with an insulator in three types, including I-type, V-type, and strain-type. The response comprises the background and resonant component. It is found that the background component constitutes a major part of the response, and the resonant component is closely related to the first symmetric out-of-plane mode. Furthermore, the closed-form solution is discussed and validated by the aeroelastic wind tunnel testing in the frequency domain. Based on the experimental data, this study provides a theoretical method for predicting wind-induced loads on transmission tower structures.
dc.publisherASCE
dc.titleAeroelastic Wind Tunnel Testing on the Wind-Induced Dynamic Reaction Response of Transmission Line
dc.typeJournal Paper
dc.journal.volume34
dc.journal.issue1
dc.journal.titleJournal of Aerospace Engineering
dc.identifier.doi10.1061/(ASCE)AS.1943-5525.0001223
dc.journal.fristpage04020105
dc.journal.lastpage04020105-11
dc.page11
dc.treeJournal of Aerospace Engineering:;2021:;Volume ( 034 ):;issue: 001
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record