dc.description.abstractIn this study, cooling degree day (CDD) and life cycle cost (LCC) analyses are applied to refrigerated warehouses in Turkey to determine the optimum insulation thickness. The external wall of refrigerated warehouses is considered as a sandwich wall and the insulation material is taken to be expanded polystyrene. Also, the base temperatures are assumed to be −20°C, −18°C, −12°C, 0°C, and 6°C, while coefficient of performance (COP) values are 1.2, 1.5, 1.8, 2.1, and 2.5. As a result: (1) the insulation thickness is directly proportional to the insulation cost; (2) insulation thickness is inversely proportional to the electricity cost; (3) the maximum annual energy saving is found for a COP of 1.2, and the minimum rate is determined for a COP value of 2.5; (4) the maximum and minimum energy savings are found for −20°C and 6°C, respectively; (5) the maximum total cost is found for COP=1.2; (6) CO2 emissions increase with increases in CDD for the unit surface area; and (7) an increase in COP values reduces CO2 emissions.
dc.publisherAmerican Society of Civil Engineers
dc.titleLife-Cycle Cost, Cooling Degree Day, and Carbon Dioxide Emission Assessments of Insulation of Refrigerated Warehouses Industry in Turkey
dc.typeJournal Paper
dc.journal.volume145
dc.journal.issue10
dc.journal.titleJournal of Environmental Engineering
dc.identifier.doi10.1061/(ASCE)EE.1943-7870.0001575
dc.page04019062