Show simple item record

dc.contributor.authorJin Kim, Hyun
dc.contributor.authorLiebenberg, Leon
dc.contributor.authorJacobi, Anthony M.
dc.date.accessioned2019-02-28T11:00:56Z
dc.date.available2019-02-28T11:00:56Z
dc.date.copyright5/7/2018 12:00:00 AM
dc.date.issued2018
dc.identifier.issn0022-1481
dc.identifier.otherht_140_09_091501.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4251743
dc.description.abstractHeat transfer and pressure drop characteristics of R-134a boiling in a chevron-patterned brazed plate heat exchanger (BPHE) are studied experimentally. With corrugated BPHE channels having hydraulic diameter of 3.4 mm and low refrigerant mass flux, boiling near the micro-macroscale transition is speculated. Heat exchanger performance is characterized with varying mass flux (30–50 kgm−2s−1), saturation pressure (675 kPa and 833 kPa), heat flux (0.8 and 2.5 kWm−2), and vapor quality (0.1–0.9). The two-phase refrigerant heat transfer coefficient increases with heat flux as often observed during nucleate boiling. It also weakly increases with saturation pressure and the associated lower latent heat during convective boiling; heat transfer is improved by the decreased liquid film thickness surrounding confined bubbles inside the narrow BPHE channels, which is the main characteristic of microscale boiling. As often observed in macroscale boiling, the inertial forces of the liquid and vapor phases cause an unsteady annular film, leading to premature partial dryout. The onset of dryout is accelerated at the lower saturation pressure, due to increased surface tension, another microscale-like characteristic. Higher surface tension retains liquid in sharp corners of the corrugated channel, leaving lateral surface areas of the wall dry. Two-phase pressure drop increases with mass flux and vapor quality, but with decreasing saturation pressure. Dryout decreases the friction factor due to the much lower viscosity of the gas phase in contact with the wall. Several semi-empirical transition criteria and correlations buttress the current analyses that the thermal-fluidic characteristics peculiar to BPHEs might be due to macro-microscale transition in boiling.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleConvective Boiling of R-134a Near the Micro-Macroscale Transition Inside a Vertical Brazed Plate Heat Exchanger
dc.typeJournal Paper
dc.journal.volume140
dc.journal.issue9
dc.journal.titleJournal of Heat Transfer
dc.identifier.doi10.1115/1.4039397
dc.journal.fristpage91501
dc.journal.lastpage091501-10
dc.treeJournal of Heat Transfer:;2018:;volume( 140 ):;issue: 009
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record