    Hybrid Dynamic-Empirical Building Energy Modeling Approach for an Existing Campus Building

    Thumbnail
    View/Open
    %28ASCE%29AE.1943-5568.0000183.pdf (1.708Mb)
    Date
    2016
    Author
    William O. Collinge
    Justin C. DeBlois
    Amy E. Landis
    Laura A. Schaefer
    Melissa M. Bilec
    Metadata
    Show full item record
    Abstract
    A hybrid modeling framework was constructed to investigate the uncertainty in modeling the energy consumption of an existing campus building with minimal instrumentation. The hybrid framework consisted of a dynamic model of the building’s conditioned spaces, coupled with an empirical model of the building’s HVAC system. The empirical model was calibrated using linear regression of available HVAC system temperature and flow measurements from a building automation system to develop estimates of internal loads and relationships between envelope heat gains/losses and indoor/outdoor temperatures. Crabtree Hall, a 40-year-old building at the University of Pittsburgh, was used as an illustrative case study for this approach. A separate data collection time frame was used for empirical model verification in addition to the initial model development time frame. Comparative results from the model showed a 20% normalized RMS deviation for hourly net heating and cooling for the average day in a given month. This close agreement highlights the possibilities of this approach for rapid assessment of energy consumption and retrofit potential in existing buildings. Future work will include additional refinement of the components of energy consumption using mobile equipment to collect targeted measurements at additional locations, as well as cross-checking existing measurement locations. Additional future work should include extending this method to buildings with more complex HVAC systems, such as variable-air-volume systems and multiple thermal zones, to further verify and improve its robustness.
    URI
    http://138.201.223.254:8080/yetl1/handle/yetl/4245074
    Collections
    • Journal of Architectural Engineering

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV