dc.description.abstractFan efficiency is known to increase with size. In part I of this study, savings in server fan power on the order of 50% were reported by replacing server-enclosed 60 mm fans with a rear-mounted wall of larger fans (80 mm or 120 mm in size). A methodology for row-wise control of such rack-level fans, with the purpose of simulating an actual product, is previewed and savings comparable to part I are reported. Performance under real-life scenarios such as nonuniform computational loads and fan failure is investigated. Each rack-level setup has distinct advantages. Selecting between configurations would necessitate a compromise between efficiency, redundancy, and cost.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleEffectiveness of Rack-Level Fans—Part II: Control Strategies and System Redundancy
dc.typeJournal Paper
dc.journal.volume139
dc.journal.issue4
dc.journal.titleJournal of Electronic Packaging
dc.identifier.doi10.1115/1.4038014
dc.journal.fristpage41012
dc.journal.lastpage041012-9