| dc.description.abstract | Fan efficiency is known to increase with size. In part I of this study, savings in server fan power on the order of 50% were reported by replacing server-enclosed 60 mm fans with a rear-mounted wall of larger fans (80 mm or 120 mm in size). A methodology for row-wise control of such rack-level fans, with the purpose of simulating an actual product, is previewed and savings comparable to part I are reported. Performance under real-life scenarios such as nonuniform computational loads and fan failure is investigated. Each rack-level setup has distinct advantages. Selecting between configurations would necessitate a compromise between efficiency, redundancy, and cost. | |
| dc.publisher | The American Society of Mechanical Engineers (ASME) | |
| dc.title | Effectiveness of Rack-Level Fans—Part II: Control Strategies and System Redundancy | |
| dc.type | Journal Paper | |
| dc.journal.volume | 139 | |
| dc.journal.issue | 4 | |
| dc.journal.title | Journal of Electronic Packaging | |
| dc.identifier.doi | 10.1115/1.4038014 | |
| dc.journal.fristpage | 41012 | |
| dc.journal.lastpage | 041012-9 | |
| dc.tree | Journal of Electronic Packaging:;2017:;volume( 139 ):;issue: 004 | |
| dc.contenttype | Fulltext | |