dc.description.abstractComplete immersion of servers in dielectric mineral oil has recently become a promising technique for minimizing cooling energy consumption in data centers. However, a lack of sufficient published data and long-term documentation of oil immersion cooling performance make most data center operators hesitant to apply these approaches to their mission critical facilities. In this study, a single server was fully submerged horizontally in mineral oil. Experiments were conducted to observe the effects of varying the volumetric flow rate and oil inlet temperature on thermal performance and power consumption of the server. Specifically, temperature measurements of the central processing units (CPUs), motherboard (MB) components, and bulk fluid were recorded at steady-state conditions. These results provide an initial bounding envelope of environmental conditions suitable for an oil immersion data center. Comparing with results from baseline tests performed with traditional air cooling, the technology shows a 34.4% reduction in the thermal resistance of the system. Overall, the cooling loop was able to achieve partial power usage effectiveness (pPUECooling) values as low as 1.03. This server level study provides a preview of possible facility energy savings by utilizing high temperature, low flow rate oil for cooling. A discussion on additional opportunities for optimization of information technology (IT) hardware and implementation of oil cooling is also included.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleThermal Performance and Efficiency of a Mineral Oil Immersed Server Over Varied Environmental Operating Conditions
dc.typeJournal Paper
dc.journal.volume139
dc.journal.issue4
dc.journal.titleJournal of Electronic Packaging
dc.identifier.doi10.1115/1.4037526
dc.journal.fristpage41005
dc.journal.lastpage041005-9
dc.treeJournal of Electronic Packaging:;2017:;volume( 139 ):;issue: 004
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record