dc.description.abstractIn a raised floor data center, cold air from a pressurized subfloor plenum reaches the data center room space through perforated floor tiles. Presently, commercial tool “Flow Hood” is used to measure the tile air flow rate. Here, we will discuss the operating principle and the shortcomings of the commercial tool and introduce two other tile air flow rate measurement tools. The first tool has an array of thermal anemometers (named as “Anemometric Tool”), and the second tool uses the principle of temperature rise across a known heat load to measure the tile air flow rate (named as “Calorimetric Tool”). The performance of the tools is discussed for different types of tiles for a wide range of tile air flow rates. It is found that the proposed tools result in lower uncertainty and work better for high porosity tiles, as compared to the commercial tool.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleMeasurement of Air Flow Rate Through Perforated Floor Tiles in a Raised Floor Data Center
dc.typeJournal Paper
dc.journal.volume139
dc.journal.issue1
dc.journal.titleJournal of Electronic Packaging
dc.identifier.doi10.1115/1.4035596
dc.journal.fristpage11007
dc.journal.lastpage011007-8
dc.treeJournal of Electronic Packaging:;2017:;volume( 139 ):;issue: 001
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record