Show simple item record

dc.contributor.authorSherer, II ,Thomas H.
dc.contributor.authorJoshi, Yogendra
dc.date.accessioned2017-05-09T01:27:33Z
dc.date.available2017-05-09T01:27:33Z
dc.date.issued2016
dc.identifier.issn1528-9044
dc.identifier.otherep_138_03_031008.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/160831
dc.description.abstractSolid liquid phasechange materials (PCMs) present a promising approach for reducing data center cooling costs. We review prior research in this area. A shellandtube PCM thermal energy storage (TES) unit is then analyzed numerically and experimentally. The tube bank is filled with commercial paraffin RUBITHERM RT 28 HC PCM, which melts as the heat transfer fluid (HTF) flows across the tubes. A fully implicit onedimensional control volume formulation that utilizes the enthalpy method for phase change has been developed to determine the transient temperature distributions in both the PCM and the tubes themselves. The energy gained by a column of tubes is used to determine the exit bulk HTF temperature from that column, ultimately leading to an exit HTF temperature from the TES unit. This paper presents a comparison of the numerical and experimental results for the transient temperature profiles of the PCMfilled tubes and HTF.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleNumerical and Experimental Investigation of Shell and Tube Phase Change Material Thermal Energy Storage Unit
dc.typeJournal Paper
dc.journal.volume138
dc.journal.issue3
dc.journal.titleJournal of Electronic Packaging
dc.identifier.doi10.1115/1.4034101
dc.journal.fristpage31008
dc.journal.lastpage31008
dc.identifier.eissn1043-7398
dc.treeJournal of Electronic Packaging:;2016:;volume( 138 ):;issue: 003
dc.contenttypeFulltext