Show simple item record

dc.contributor.authorMu, Baojie
dc.contributor.authorLi, Yaoyu
dc.contributor.authorSeem, John E.
dc.contributor.authorHu, Bin
dc.date.accessioned2017-05-09T01:16:48Z
dc.date.available2017-05-09T01:16:48Z
dc.date.issued2015
dc.identifier.issn0022-0434
dc.identifier.otherds_137_11_111011.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/157635
dc.description.abstractThis paper presents a multivariable Newtonbased extremum seeking control (ESC) scheme for efficient operation of a chilledwater plant. A modelicabased dynamic simulation model of the chilledwater plant consists of one screw chiller and one counterflow cooling tower was adopted for evaluation of proposed twoinput Newtonbased ESC controller. The ESC controller takes the total power of the chiller compressor, the coolingtower fan, and the condenser water (CW) pump as feedback signal and discovers the optimum outputs of coolingtower fan speed and the condenserloop water flow rate to maximize the power efficiency in real time with the cooling load being satisfied. Remarkable energy saving is observed for several testing conditions.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleA Multivariable Newton Based Extremum Seeking Control for Condenser Water Loop Optimization of Chilled Water Plant
dc.typeJournal Paper
dc.journal.volume137
dc.journal.issue11
dc.journal.titleJournal of Dynamic Systems, Measurement, and Control
dc.identifier.doi10.1115/1.4031051
dc.journal.fristpage111011
dc.journal.lastpage111011
dc.identifier.eissn1528-9028
dc.treeJournal of Dynamic Systems, Measurement, and Control:;2015:;volume( 137 ):;issue: 011
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record