    Thermal Characteristics of Open and Contained Data Center Cold Aisle

    Thumbnail
    View/Open
    ht_135_6_061901.pdf (2.963Mb)
    Date
    2013
    Author
    Arghode, Vaibhav K.
    Sundaralingam, Vikneshan
    Joshi, Yogendra
    Phelps, Wally
    Metadata
    Show full item record
    Abstract
    Cold aisle containment is used in raised floor, air cooled data centers to minimize direct mixing between the supplied cold air and the hot air exiting from the servers. The objective of such a system is to minimize the server inlet air temperatures. In this paper, large scale air temperature field measurements are performed to investigate the hot air entrainment characteristics in the cold aisle in both open and contained aisle conditions. Both underprovisioned and overprovisioned scenarios were examined. Thermal field measurements suggest significant improvement in the cold air delivery for the case with contained aisle as compared to open aisle. Even for an overprovisioned case with open aisle, hot air entrainment was observed from the aisle entrance; however, for the contained aisle condition, close to perfect cold air delivery to the racks was observed. For both underprovisioned and overprovisioned cases, the aisle containment tended to equalize the tile and rack air flow rates. Balance air is expected to be leaked into or out of the containment to makeup the flow rate difference for the contained aisle condition. The CFD modeling strategy at the aisle level is also discussed for open aisle condition. Our previous investigation for rack level modeling has shown that consideration of momentum rise above the tile surface improves the predictive capability as compared to the generally used porous jump model. The porous jump model only specifies a step pressure loss at the tile surface without any influence on flow field. The momentum rise above the tile surface was included using a modified body force model by artificially specifying a momentum source above the tile surface. The modified body force model suggested higher air entrainment and higher reach of cold air as compared to the porous jump model. The modified body force model was able to better capture hot air entrainment through aisle entrance and compared well with the experimental data for the end racks. The generally used porous jump model suggested lower hot air entrainment and under predicted the server inlet temperatures for end racks.
    URI
    http://yetl.yabesh.ir/yetl/handle/yetl/152145
    Collections
    • Journal of Heat Transfer

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV