Effects of Tube Row on Heat Transfer and Surface Wetting of Microscale Porous Layer Coated, Horizontal Tube, Falling Film Evaporator
View/ Open
Date
2013Author
Kأ¶roؤںlu, Batikan
Bogan, Nicholas
Park, Chanwoo
Metadata
Show full item recordAbstract
An experimental study was conducted to investigate the effects of tube row on surface wetting and heat transfer of a horizontaltube, fallingfilm evaporator. Two types of the evaporator tubes were used for comparison: plain copper and copper coated with a microscale porouslayer. Distilled water was used as solution and heating fluids. A visual observation experiment performed in ambient with no heat input showed that when solution fluid was dripped onto the evaporator tubes from a solution dispenser, the plain tubes were partially wetted, while the porouslayer coated tubes were completely wetted due to capillary liquid spreading, even at low solution flow rates. It was found from the heat transfer experiment performed in a closed chamber under saturated conditions that the porouslayer coated tubes exhibited superior evaporation heat transfer (up to 100% overall improvement over the plain tubes at low solution flow rates) due to complete solution wetting and thinfilm evaporation. It was also observed that the surface wetting and heat transfer are greatly influenced by both intertube flow mode of solution fluid and tube wall superheat. The effects of the tube row on the solution wetting and heat transfer were significant, especially for downstream tubes.