Show simple item record

dc.contributor.authorEmad Samadiani
dc.contributor.authorYogendra Joshi
dc.contributor.authorHendrik Hamann
dc.contributor.authorMadhusudan K. Iyengar
dc.contributor.authorSteven Kamalsy
dc.contributor.authorJames Lacey
dc.date.accessioned2017-05-09T00:52:21Z
dc.date.available2017-05-09T00:52:21Z
dc.date.copyrightApril, 2012
dc.date.issued2012
dc.identifier.issn0022-1481
dc.identifier.otherJHTRAO-27938#041401_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/149486
dc.description.abstractIn this paper, an effective and computationally efficient proper orthogonal decomposition (POD) based reduced order modeling approach is presented, which utilizes selected sets of observed thermal sensor data inside the data centers to help predict the data center temperature field as a function of the air flow rates of computer room air conditioning (CRAC) units. The approach is demonstrated through application to an operational data center of 102.2 m2 (1100 square feet) with a hot and cold aisle arrangement of racks cooled by one CRAC unit. While the thermal data throughout the facility can be collected in about 30 min using a 3D temperature mapping tool, the POD method is able to generate temperature field throughout the data center in less than 2 s on a high end desktop personal computer (PC). Comparing the obtained POD temperature fields with the experimentally measured data for two different values of CRAC flow rates shows that the method can predict the temperature field with the average error of 0.68 °C or 3.2%. The maximum local error is around 8 °C, but the total number of points where the local error is larger than 1 °C, is only ∼6% of the total domain points.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleReduced Order Thermal Modeling of Data Centers via Distributed Sensor Data
dc.typeJournal Paper
dc.journal.volume134
dc.journal.issue4
dc.journal.titleJournal of Heat Transfer
dc.identifier.doi10.1115/1.4004011
dc.journal.fristpage41401
dc.identifier.eissn1528-8943
dc.keywordsTemperature
dc.keywordsSensors
dc.keywordsModeling
dc.keywordsData centers AND Errors
dc.treeJournal of Heat Transfer:;2012:;volume( 134 ):;issue: 004
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record