    From Chip to Cooling Tower Data Center Modeling: Influence of Server Inlet Temperature and Temperature Rise Across Cabinet

    Thumbnail
    View/Open
    JEPAE4-26312#011004_1.pdf (357.5Kb)
    Date
    2011
    Author
    Thomas J. Breen
    Jeff Punch
    Amip J. Shah
    Cullen E. Bash
    Ed J. Walsh
    Metadata
    Show full item record
    Abstract
    To achieve reductions in the power consumption of the data center cooling infrastructure, the current strategy in data center design is to increase the inlet temperature to the rack, while the current strategy for energy-efficient system thermal design is to allow increased temperature rise across the rack. Either strategy, or a combination of both, intuitively provides enhancements in the coefficient of performance of the data center in terms of computing energy usage relative to cooling energy consumption. However, this strategy is currently more of an empirically based approach from practical experience, rather than a result of a good understanding of how the impact of varying temperatures and flow rates at rack level influences each component in the chain from the chip level to the cooling tower. The aim of this paper is to provide a model to represent the physics of this strategy by developing a modeling tool that represents the heat flow from the rack level to the cooling tower for an air cooled data center with chillers. This model presents the performance of a complete data center cooling system infrastructure. After detailing the model, two parametric studies are presented that illustrate the influence of increasing rack inlet air temperature, and temperature rise across the rack, on different components in the data center cooling architecture. By considering the total data center, and each component’s influence on the greater infrastructure, it is possible to identify the components that contribute most to the resulting inefficiencies in the heat flow from chip to cooling tower and thereby identify the components in need of possible redesign. For the data center model considered here it is shown that the strategy of increasing temperature rise across the rack may be a better strategy than increasing inlet temperature to the rack.
    URI
    http://yetl.yabesh.ir/yetl/handle/yetl/145819
    Collections
    • Journal of Electronic Packaging

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV