Show simple item record

dc.contributor.authorM. H. M. Grooten
dc.contributor.authorC. W. M. van der Geld
dc.date.accessioned2017-05-09T00:38:58Z
dc.date.available2017-05-09T00:38:58Z
dc.date.copyrightMay, 2010
dc.date.issued2010
dc.identifier.issn0022-1481
dc.identifier.otherJHTRAO-27887#051501_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/143859
dc.description.abstractWhen traditional air-to-air cooling is too voluminous, long thermosyphons may offer a way out. For safe operation of heat exchangers equipped with thermosyphons, the limiting heat flux qlim″ is an important design parameter. Some literatures are found to deal with the operation limiting heat flux of closed two-phase thermosyphons. However, R-134a filled thermosyphons with large length-to-diameter (188) are hardly investigated up to now. Extrapolation of existing correlations to predict qlim″ in this case results in large scatter. The effect of the angle of inclination on qlim″ has not been considered until now. Dedicated experiments with a single thermosyphon with a large length-to-diameter ratio (188) and filled with R-134a are presented and analyzed. Effects of saturation temperature, filling ratio, and angle of inclination β on the operational limiting heat flux have been investigated. The thermosyphon functions properly if β<83 deg, and qlim″ is found to increase with increasing β. With decreasing saturation temperature, qlim″ increases. The filling ratio is found not to be crucial if it exceeds 25%. Correlations are presented to accurately predict the operation limiting heat flux for thermosyphons with a L/d ratio up to 188. Because of the accounting for the above new aspects, these correlations are also relevant for filling refrigerants other than R-134a.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleThe Effect of the Angle of Inclination on the Operation Limiting Heat Flux of Long R-134a Filled Thermosyphons
dc.typeJournal Paper
dc.journal.volume132
dc.journal.issue5
dc.journal.titleJournal of Heat Transfer
dc.identifier.doi10.1115/1.4000441
dc.journal.fristpage51501
dc.identifier.eissn1528-8943
dc.treeJournal of Heat Transfer:;2010:;volume( 132 ):;issue: 005
dc.contenttypeFulltext