Show simple item record

dc.contributor.authorEmad Samadiani
dc.contributor.authorHrishikesh Amur
dc.contributor.authorYogendra Joshi
dc.contributor.authorKarsten Schwan
dc.contributor.authorBhavani Krishnan
dc.date.accessioned2017-05-09T00:37:13Z
dc.date.available2017-05-09T00:37:13Z
dc.date.copyrightSeptember, 2010
dc.date.issued2010
dc.identifier.issn1528-9044
dc.identifier.otherJEPAE4-26306#031006_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/142948
dc.description.abstractConcurrency and exchanging design knowledge among thermal and IT management are required to achieve an energy efficient operational data center. In this paper, a design approach is presented to bring adaptability and concurrency for coordinated minimization of cooling and IT power consumption in data centers. The presented approach is centered on a proper orthogonal decomposition based reduced order thermal modeling approach, and power profiling of the IT equipment to identify the optimal parameters of the air cooling systems along with optimal dynamic workload distribution among the servers. The method is applied to a data center cell with different rack and server architectures. The results show that the design approach results in 12–70% saving in the total energy consumption of the data center cell for various scenarios, compared with a baseline design.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleCoordinated Optimization of Cooling and IT Power in Data Centers
dc.typeJournal Paper
dc.journal.volume132
dc.journal.issue3
dc.journal.titleJournal of Electronic Packaging
dc.identifier.doi10.1115/1.4001858
dc.journal.fristpage31006
dc.identifier.eissn1043-7398
dc.keywordsCooling
dc.keywordsDesign
dc.keywordsData centers
dc.keywordsModeling
dc.keywordsOptimization AND Temperature
dc.treeJournal of Electronic Packaging:;2010:;volume( 132 ):;issue: 003
dc.contenttypeFulltext